Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
PROFINET / Modbus TCP Master
Document code: MN67611_ENG Revision 1.001 Page 14 of 29
SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, PROFINET and Modbus.
By Pressing the “
Set Communication
” button from the main window for SW67611 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
The window is divided in two sections, one for the PROFINET and the other for the Modbus TCP Master.
The means of the fields for “PROFINET” are:
In the fields “
IP ADDRESS
” insert the IP address that you want to give to the Converter
(PROFINET side);
In the fields “
SUBNET
Mask
” insert the SubNet Mask (PROFINET side);
In the fields “
GATEWAY
” insert the default gateway that you want to use. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net
(PROFINET side);
In the field “
Port
” the port used for PROFINET communication is defined. The port has a fixed value
of 34964;
In the field "
PROFINET Name of Station
" is possible to assign a name to the PROFINET node;
In the field “
Number Byte IN
” insert the number of input byte of the slave station;
In the field “
Number Byte Out
” insert the number of output byte of the slave station;
In the field “
Diagnostic
” insert the starting byte of the PROFINET array where you will save the
diagnostic of Modbus. It is possible to enable/disable this function using the checkbox.
For more informations about the diagnostic, see “Diagnostic” section on page 19.
Figure 3: “Set Communication” window