Document code: MN67801_ENG Revision 1.100 Pagina 18 di 31
SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, KNX and BACnet.
By Pressing the “
Set Communication
” button from the main window for SW67801 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
The window is divided in two sections, one for the KNX and one for the BACnet.
In the section “BACnet Type” is possible to select the type of BACnet to use from:
BACnet/IP (it uses ethernet);
BACnet MS/TP (it uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the fields “
IP ADDRESS
” insert the IP address that you want to give to the Converter;
In the fields “
SUBNET
Mask
” insert the SubNet Mask;
In the fields “
GATEWAY
” insert the default gateway that you want to use. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “
Port
” the port used for BACnet communication is defined. The default port used for
BACnet communication is 47808, but is possible to insert any value (except 10000 and 10001);
In the field "
BACnet Device Name
" is possible to assign a name to the BACnet node;
In the field “
Device Istance
” is possible to assign a number to the BACnet node (Used for the
Device Istance).
In the field “
TimeOut (ms)
” the timeout for the BACnet requests is defined.
The means of the fields for “KNX” are:
In the field “
Type
” the type of KNX is defined (fixed to ‘KNX TP’);
In the field “
ID Device
” the ID of the KNX side of the converter is defined.
Figure 3a: “Set Communication”
window