If selected “BACnet MS/TP” the means of the fields for “BACnet” are:
In the field “
Baudrate
” it is possible to select the baudrate of the BACnet line (1200, 2400,
4800, 9600, 19200, 38400, 57600, 115200);
In the field “
Parity
” it is possible to select the parity of the line (None, Odd, Even);
In the field “
BACnet Device Name
” is possible to insert the name to give to the BACnet node
(maximum 17 characters);
In the field “
MAC Address
” is possible to define the MAC of BACnet node (from 0 to 254);
The field “
Max Masters
” specifies the highest allowable address for master nodes. The value
shall be less than or equal to 127;
The field “
Max Info Frames
” specifies the maximum number of information frames the node
may send before it must pass the token;
In the field “
Device Istance
” is possible to assign a number to the BACnet node (Used for the
Device Istance).
The means of the fields for the “Ethernet Update” section are:
In the fields “
IP ADDRESS
” insert the IP address that you want to give to the Converter;
In the fields “
SUBNET
Mask
” insert the SubNet Mask;
In the fields “
GATEWAY
” insert the default gateway that you want to use. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net.
These information are used for programming the Converter.
The means of the fields for “KNX” are:
In the field “
Type
” the type of KNX is defined (fixed to ‘KNX TP’);
In the field “
ID Device
” the ID of the KNX side of the converter is defined.
Figure 3b: “Set Communication” window