ADICOS GSME
405-2010-003 EN52
FUnCTIOn
4.1.2.6
Customized configuration changes
Using the ADICOS service software, all limit values of the ADICOS GSME can be change inde
-
pendently from the delivered basic configuration. If the limit values of the basic configuration
are replaced with freely selected limit values, an individual detector configuration is chosen.
Faulty limit value combinations can lead to complete ineffectiveness of the de
-
tector!
•
The detector parameters may only be changed by experienced specialist
personnel!
•
In case of doubt, contact the manufacturer!
4.2
LED signals
The current operating condition of the detector is indicated by three signal LEDs on the front
of the detector. The following table explains the illumination states.
LED
State
Function
green
flashing
Initialization /not ready for operation yet
on
Normal operation
off
Detector system off/detector, fuse, or cable defective
yellow
on
Detector fault
off
Normal operation
with BMZ module:
red
off
Normal operation
on
Alarm to central fire alarm panel
flashing
Detector alarm, however, without central fire alarm panel alarm
with pre-alarm module:
red
off
Normal operation
on
Alarm
flashing
Pre-alarm
without BMZ module:
red
off
Normal operation
on
Alarm