Replacing the configuration module
NOTICE!!
Property damage due to electrical voltage
Electrical voltages during wiring work can cause damage to property.
•
De-energize the entire detector system for any wiring
and secure against
unintentional reactivation!
•
Apply ESD measures when working on the detector electronics!
•
Do not touch electronic components!
The configuration module is a compact electronics module, which is populated in the factory
configuration in the configuration module slot of the detector. It is used to define the resis
-
tances of the signal limit contacts of the detector. Configuration modules must be replaced on
site in special cases.
Replacing the configuration module
1
Using the PZ2 screwdriver, loosen the enclosure screws
in the detector cover
The screws remain in the cover.
2
Carefully remove the enclosure cover with the detector
electronics
The plug connector for detector connection remains
connected.
3
Carefully pull off the old configuration module
4
Insert the new configuration module in the correct
orientation into the configuration module slot on the
detector board
5
Close the detector enclosure