11
ADICOS GSME
405-2010-003 EN52
STRUCTURE
The BMZ module slot is a coded, 10-pin connector above the gas
sensors on the detector board.
Depending on the ordered configuration, it is eqiupped in the facto
-
ry configuration with a BMZ board, which enables integration of the
detector in external fire alarm systems.
As an alternative, the pre-alarm module can be inserted here.
v
v
Slots “fuses”
There are two slots for fuses at the bottom left on the detector
board. These are marked with labels F201 and F203.
In the factory configuration, the fuse slots are equipped with one
slow burning 500 mA fuse each.
v
v
3.4
Cable assignment
Color
Signal
Potential-free contact
red
Operating voltage
24 ... 40 V DC non-polarized
black
yellow
Relay output X6 i
Alarm (NO)
1
white
Relay output X6 o
Alarm (NO)
1
brown
Relay output X7 o
Failure (NC)
1
green
Relay output X7 i
Failure (NC)
1