21
ADICOS GSME
405-2010-003 EN52
InSTALLATIOn
5.2
Installation orientation
NOTICE!!
A sintered metal filter clogged with dust deposits reduces the detectivity
of the detector and can lead to ineffectiveness! Water accumulation on the filter
can damage the detector.
•
Mount the detector with the sintered metal filter pointing downward!
•
Use spray protection if humidity is present!
5.3
Mounting
The ADICOS GSME detector features four M5 threaded holes for mounting. They can be found
on the rear of the enclosure.
Mounting the GSME
1
Bolt the ADICOS mounting plate
countersunk screws (included in the scope of delivery of
the mounting plate) on the rear of the detector enclosure
For ceiling mounting:
2
Drill four mounting holes arranged in a square at a dis
-
tance of 130 mm
3
Press dowels into the mounting holes
4
Attach mounting plate including detector using suitable
screws
For any other mounting location (e.g., gallows construction):
2
Bolt mounting plate including detector to the gallows con
-
struction using suitable M6 screws, nuts and lock washer
s