7 Operation
During operation, the detector monitors the fire gas concentrations captured by the sensors
per its basic configuration and triggers an alarm, when the set alarm limit values are exceeded.
The query interval of the sensors amounts to 30 seconds.
7.1
Software access
If a M-Bus interface is used, detailed detector information can
be called up via the ADICOS M-Bus. For this purpose, a service
PC with the ADICOS service software connected to the ADI-
COS central unit is required.
Using the communication number (COM or K.N.) printed on
the type plate and the front of the detector, a single view of
the detector can be called up in the software. Within this sin
-
gle view, the concentration profiles of the gas sensors can be
called up as chart, for example. The alarm thresholds of the
detector can be adjusted here as well.
Detailed information regarding the use of the ADICOS service
software as well as the specific approach to changing the detector settings is available upon
request.
7.2
Alarm
If the gas concentrations detected by the detector sensors ex
-
ceed the set alarm thresholds, the detector triggers an alarm.
The internal alarm relay is activated and the red signal LED is
illuminated (without BMZ module). The alarm result is relayed
to the connected BMZ via the ADICOS M-Bus resp. fire alarm
lines.
If an alarm delay
is adjusted, the alarm state
is only initiated, once the alarm condition is met over the set
duration.
BMZ operation
If the detector is connected to a central fire alarm panel, the alarm result is transmitted to the
central fire alarm panel via the BMZ module. The BMZ switches the detector in alarm state and
the alarm relay as well as the red signal LED of the detector are switched on. If the BMZ does
not switch the ADICOS GSME into alarm state, the red signal LED flashes.
7.2.1
Resetting the alarm
The ADICOS GSME remains in alarm state, as long as the alarm condition is met. The state is
newly determined in every query cycle (30 seconds interval). As soon as the alarm condition is
not met, the alarm state is automatically reset. Signal LED »Alarm« is only reset after a respec
-
GSME-M4
G000001
20...40 / 14
408-2001-201
2 x
0,5
A
64
2017
G0000001
GTE
Ind
ustr
iee
lek
tro
nik
Gm
bH
Advanced Discovery System
TYPE
ANR
COM
SERIAL
YR
IP
V
DC
/ VA
I
S
≤
°C
-20
≤
T
a
≤ 50
COM-Nummer