33
ADICOS GSME
405-2010-003 EN52
MAInTEnAnCE
8.3
Function test of the signal relays
The “Alarm” and “Fault” signal relays must be checked for function quarterly. For this purpose,
they can be switched for test purposes via the ADICOS service software.
The function test of the signal relays triggers an alarm resp. fault state in the
connected central fire alarm panel.
•
Switch the BMZ into inspection mode prior to the function test!
8.4 Annual function test
To ensure correct function of the detector, a test with the ADICOS GTL-3 tester
is required.
•
Perform at least one test triggering per year with the GTL-3!
•
Observe GTE instructions no. 430-2410-102!
The function test of the detector triggers an alarm state in the connected cen
-
tral fire alarm panel.
•
Switch the BMZ into inspection mode prior to the function test!
8.5 Detector replacement
The maximum service life of the sensors of the ADICOS GSME detector is limited to eight
years. Depending on the aggressiveness of the usage environment, the sensitivity of the sen
-
sor can also decline earlier and make a detector replacement necessary.
Replace ADICOS GSME detectors no later than eight years after commissioning!
The same information apply to detector replacement like for their initial installation
Proceed as follows to replace the detector:
8.5.1
Save inventory data
Save the inventory data if any of these cases apply:
–
The ADICOS central software is used permanently for monitoring measurement data.
–
The alarm thresholds of the old units do not correspond to the alarm thresholds of the new
units and should be available for data transfer.
To save the inventory data of a detector, an installed ADICOS central software
is required.