GSME-X22

Supplementary Instructions Manual

Fire Gas Detector GSME

®

Summary of Contents for GSME-X22

Page 1: ...EN GTE Industrieelektronik GmbH Helmholtzstr 21 38 40 41747 Viersen Germany 49 2162 3703 0 info gte de GSME X22 Supplementary Instructions Manual Fire Gas Detector GSME ...

Page 2: ...ektronik GmbH Helmholtzstr 21 38 40 41747 Viersen GERMANY Support hotline 49 2162 3703 0 E Mail support adicos gte de 2020 GTE Industrieelektronik GmbH This document and all figures contained may not be copied changed or distributed without explicit approval by the manufacturer Subject to technical changes ADICOS and GSME are registered trademarks of GTE Industrieelektronik GmbH ...

Page 3: ...nter ference resistant fulfillment of the detection objective defined during planning via suitable layout and parameterization The detector units are connected using the ADICOS M bus to a central unit which enables voltage supply and parameterization of every individual detector and which stores all sensor data for statistical analyses ADICOS X22 Detectors are designed for for operation within exp...

Page 4: ...Intended use 2 2 2 Standards and regulations 2 2 3 Personnel qualification 3 2 4 Handling electrical voltage 3 2 5 Modification 3 3 Structure 4 3 1 Overview 4 3 3 Type plate information 6 4 Installation 7 4 1 Mounting 7 4 2 Wiring 8 5 Commissioning 8 6 Operation 8 3 2 Cable assignment 5 7 Maintenance Detector replacement 9 8 Technical Data 10 9 Appendix ADICOS mounting plate 11 ...

Page 5: ...This manual features a continuous structure for best possible comprehension The following labels are used Warning signs This manual uses the following information types NOTE This information type provides information directly important for further system operation WARNING This information type signals a danger that can lead to fatal or severe injuries DANGER This information type signals a danger ...

Page 6: ...ers described in Chap 8 Technical data must be met Any deviating use requires prior consultation with the manufacturer Compliance with this manual as well as all applicable country specific provisions is also part of the intended use 2 2 Standards and regulations The safety and accident prevention regulations applicable for the specific application must be observed during detector installation com...

Page 7: ...l WARNING Installation commissioning parameterization and maintenance may only be performed by authorized and respectively trained personnel 2 4 Handling electrical voltage DANGER The electronics of ADICOS X22 Detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres Do not open enclosure De energize the entire detector system and secure against ...

Page 8: ...Structure 4 ADICOS X22 Melder 405 2010 003 EN21 3 Structure 3 1 Overview 100 100 28 1 2 3 4 5 No Description Enclosure Display elements GSME spray protection Sinter metal filter Cable gland ...

Page 9: ...Wire Color Signal Analog signal 5 black Analog signal protected against polarity reversal 4 20 mA 6 black Analog signal protected against polarity reversal 0 5 V 0 10 V 5 white Analog signal 4 20 mA 6 white Analog signal 0 V Option Fire panel interface Wire Color Interface module Siemens FDnet Bosch LSNi 5 black Interface module A in FDnet LSN a in 5 white Interface module B in FDnet A LSN b1 in 6...

Page 10: ...e ADICOS X22 Detectors contains the following information NOTE Until 12 2014 some ADICOS X22 Detectors have been labeled as ADICOS Ex detectors GTE Industrieelektronik GmbH Typ K N IP 6X T100 C Dc 20 tamb 50 Art Bj Ik 21 6 40VDC 14VA X22 GS xx IR xxx 20xx 400 2410 0xx C II 3D Ex tc IIIC S N V VA ...

Page 11: ...7 ADICOS X22 Melder 405 2010 003 EN21 Installation 4 Installation 4 1 Mounting WARNING ADICOS X22 Detectors must be mounted with closed enclosure Do not open enclosure Use ADICOS mounting plate ...

Page 12: ...e Ex protected connection boxes with respective approval Do not bend connection cable Observe minimum bending radius Chap 8 Technical data 5 Commissioning DANGER The electronics of the ADICOS X22 Detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres Prior to switching on check that all detectors are properly mounted and wired 6 Operation DANG...

Page 13: ...ronics of the ADICOS X22 Detectors works with an electrical voltage that can trigger an explosion in potentially explosive atmospheres Do not open enclosure De energize the entire detector system and secure against unintentionally reactivation for all wiring work Replace the closed detector including connection cable only ...

Page 14: ...nsumption excl heating VA 3 5 Max Power consumption incl heating VA 14 M Bus Voltage Signal V mA max 40 V non polarised max 30 mA Thermal data TEMP 20 C Ta 50 C IP IP 64 Optional communication modules input parameters BMZ ModulSinteso FDnet V DC 33 V max 10 mA ADICOS Coupling module 4 20 mA V DC 35 V max 20 mA BMZ Modul Bosch LSN V DC 36 V max 20 mA Pre alarm relay module V DC 40 V max 10 mA V DC ...

Page 15: ...elder 405 2010 003 EN21 Appendix ADICOS mounting plate A A 1 5 0 1 5 0 1 3 0 1 3 0 6 4 A A NOTE ADICOS X22 Detectors are rated Protection by enclosure tc An Ex barrier is not mandatory 9 Appendix ADICOS mounting plate ...

Page 16: ......