6.3
Models NEO FIRE 360 to NEO FIRE 900 for Natural GAS
NEO FIRE
360
NEO FIRE
450
NEO FIRE
540
NEO FIRE
630
NEO FIRE
720
NEO FIRE
810
NEO FIRE
900
Nominal Power output
80/60 ºC
kW
350,5
438,4
526,5
614,7
703,0
791,4
880
Nominal Power output
50/30 ºC
kW
376,5
470,9
565,3
659,8
754,5
849,2
944
Nominal power input
(Qn)
kW
360
450
540
630
720
810
900
Min power output
80/60°C
kW
53,7
64,1
73,2
81,1
87,8
93,3
97,5
Min power output
50/30°C
kW
59,5
71,0
81,1
89,8
97,2
103,2
107,9
Min power input (Qn)
kW
55
65,6
75
83,1
90
95,6
100
Modulation
%
15,3%
14,6%
13,9%
13,2%
12,5%
12,0%
12,0%
η 80/60 at Qn
%
97,47%
97,52%
97,58%
97,63%
97,68%
97,74%
97,79%
η 80/60 at Qmin
%
97,79%
97,76%
97,72%
97,69%
97,66%
97,62%
97,59%
η 50/30 at Qn
%
104,72% 104,75% 104,78% 104,81% 104,83% 104,86% 104,89%
η 50/30 at Qmin
%
108,45% 108,37% 108,29% 108,22% 108,14% 108,06% 107,98%
η Partial load
%
108,81% 108,76% 108,71% 108,67% 108,62% 108,57% 108,52%
Nominal gas flow*
m3/h 36,3
45,5
54,6
63,6
72,7
81,8
91,2
Min gas flow*
m3/h 5,7
6,8
7,8
8,6
9,3
9,9
10,4
Weight w/o water
kg
400
430
460
510
540
620
690
water capacity
l
44
50
56
62
68
91
91
Max water pressure
bar
6,0
6,0
6,0
6,0
6,0
6,0
6,0
Nominal Flowrate
(Δ
T=20ºC)
m3/h 15
19
23
27
31
35
39
Min Flowrate (Δ
T=25ºC)
m3/h 12,4
15,7
19
22,3
25,6
28,9
32,3
Max Flowrate
m3/h 26
32
39
45
52
58
71
Hydraulic resistance
(Δ
T=20ºC, full load 80-
60ºC)
mbar 112
113
114
115
116
118
120
Maximum flow
temperature
ºC
90
90
90
90
90
90
90
Nominal Electrical
Power consumption
W
712
720
837
1065
1500
1800
2296
Electrical power
consumption min load
W
93
94
100
104
108
110
112
Electrical Power
consumption Stand by
W
5
5
5
5
5
5
5
Electric supply
V
1x230V
1x230V
1x230V
1x230V
1x230V
3x380V
3x380V
IP
XXD
XXD
XXD
XXD
XXD
XXD
XXD
NOx class
6
6
6
6
6
6
6
PH Condensed water
~4,0
~4,0
~4,0
~4,0
~4,0
~4,0
~4,0
Types
B
23
B
23
B
23
B
23
B
23
B
23
B
23
*
Reference conditions: 15ºC, 1013,25 mbar L.C.V=34,74 MJ/m
3
Note: data in the present document are liable to changes without prior warning.
Summary of Contents for NEO FIRE 120
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Page 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Page 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Page 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Page 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Page 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Page 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Page 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Page 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Page 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Page 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...