NEO FIRE – Technical Manual
15
6.4
Models NEO FIRE 80 to NEO FIRE 360 for PROPANE
NEO FIRE
80
NEO FIRE
120
NEO FIRE
160
NEO FIRE
200
NEO FIRE
240
NEO FIRE
280
NEO FIRE
360
Nominal Power output
80/60 ºC
kW
77,8
117
156
195
234
273
351
Nominal Power output
50/30 ºC
kW
82,4
123,5
164,6
205,7
246,7
287,7
369,0
Nominal power input
(Qn)
kW
80,0
120,0
160,0
200,0
240,0
280,0
360,0
Min power output
80/60°C
kW
13,5
20,3
27,1
33,9
40,7
47,6
61,6
Min power output
50/30°C
kW
14,9
22,3
29,8
37,2
44,6
52,0
67,0
Min power input (Qn)
kW
14
21
28
35
42
49
63
Modulation
%
17,50%
17,50%
17,50%
17,50%
17,50%
17,50%
17,50%
η 80/60 at Qn
%
97,39%
97,46%
97,53%
97,59%
97,66%
97,73%
97,53%
η 80/60 at Qmin
%
96,62%
96,78%
96,94%
97,10%
97,26%
97,42%
97,89%
η 50/30 at Qn
%
103,06% 103,00% 102,94% 102,89% 102,83% 102,77% 102,58%
η 50/30 at Qmin
%
106,35% 106,32% 106,29% 106,27% 106,24% 106,21% 106,42%
η Partial load
%
106,46% 106,45% 106,43% 106,42% 106,40% 106,39% 106,50%
Nominal gas flow*
m
3
/h 3,1
4,7
6,3
7,8
9,4
10,9
14,1
Min gas flow*
m
3
/h 0,55
0,82
1,09
1,37
1,64
1,91
2,47
Weight w/o water
kg
180
195
210
250
265
280
400
water capacity
l
12,5
15,3
18
22,9
25,6
28,4
44
Max water pressure
bar
6
6
6
6
6
6
6
Nominal Flowrate
(ΔT=20ºC)
m
3
/h 3,44
5,16
6,87
8,59
10,3
12
15
Min Flowrate
(ΔT=25ºC)
m
3
/h 2,75
4,12
5,5
6,87
8,25
9,62
12,4
Max Flowrate
m
3
/h 6,8
10,3
13,6
16,4
19,1
21,8
26
Hydraulic resistance
(ΔT=20ºC, full load 80-
60ºC)
mbar 65
80
80
90
90
100
112
Maximum flow
temperature
ºC
90
90
90
90
90
90
90
Nominal Electrical
Power consumption
W
184
194
220
294
386
471
746
Electrical power
consumption min load
W
40,0
37,0
48,0
60,0
70,0
82,0
98,0
Electrical Power
consumption Stand by
W
5
5
5
5
5
5
5
Electric supply
V
1x230V
1x230V
1x230V
1x230V
1x230V
1x230V
1x230V
IP
XXD
XXD
XXD
XXD
XXD
XXD
XXD
NOx class
6
6
6
6
6
6
6
PH Condensed water
~4,0
~4,0
~4,0
~4,0
~4,0
~4,0
~4,0
Types
B
23
, C
13
,
C
33
, C
53
B
23
, C
13
,
C
33
, C
53
B
23
, C
13
,
C
33
, C
53
B
23
, C
13
,
C
33
, C
53
B
23
, C
13
,
C
33
, C
53
B
23
, C
13
,
C
33
, C
53
B
23
*
Reference conditions: 15ºC, 1013,25 mbar. L.C.V.=88,55 MJ/m
3
Note: data in the present document are liable to changes without prior warning.
Summary of Contents for NEO FIRE 120
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Page 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Page 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Page 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Page 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Page 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Page 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Page 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Page 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Page 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Page 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...