NEO FIRE – Technical Manual
49
TYPE C33
TYPE C53:
The terminals for the supply of combustion air and for the evacuation of combustion products shall not be
installed on opposite walls of the building
The following able gives you an indication of maximum lengths for separate ducts:
Air inlet / flue outlet
Tipo
C
13
, C
33
, C
53
C
13
, C
33
, C
53
C
53
C
53
C
53
Model
Ø*
Ø110/ Ø 150 Ø 110/ Ø 200 Ø 150/ Ø 150 Ø 180/ Ø 180 Ø 200/ Ø 200
NEO FIRE 80
150
32 m
60 m
60 m
NEO FIRE 120 150
14 m
50 m
60 m
NEO FIRE 160 150
12 m
27 m
60 m
NEO FIRE 200 200
9 m
60 m
NEO FIRE 240 200
6 m
60 m
NEO FIRE 280 200
4 m
60 m
*chimney diameter
One bend 87º equal in resistance approximately 2m straight pipe
For C13 and C33 type use only system ECO-EW 316 by Jeremias.
In order to avoid condensates from the chimney goes to the heat exchanger use Length with lateral drain (left
image) or connect an elbow from boiler flues outlet to a “T” with condensate drainage.
As a flue terminal use EWEC32 (Topstub)
Summary of Contents for NEO FIRE 120
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Page 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Page 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Page 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Page 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Page 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Page 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Page 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Page 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Page 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Page 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...