NEO FIRE – Technical Manual
55
b)
A WATER TREATMENT IS ABSOLUTELY INDISPENSABLE FOR THE INSTALLATION OF THE PRIMARY
CIRCUIT IN THE FOLLOWING CASES:
Big installations (with high water contents).
Characteristics of the refilling water different from the hardness (TH) indicated in the previous table.
Frequent refillings of the installation with new water (because of drainings, water leaks, repairing), even if the
water has a hardness lower than 12ºF.
When the maximum volume allowed of refilling water is exceeded (see table).
c)
A mesh filter should be installed before each boiler (mesh of 0.3 mm).
d)
Air purging/venting:
If the boilers circuit incorporates a common vertical water manifold: place an air vent of big capacity in its
higher point.
Otherwise: it would be necessary to install an air vent of big capacity or corrosion inhibitor equipment in a high
point of the circuit behind the boilers.
e)
Old installations
e1) Before replacing the existing boilers with new boilers, proceed to clean the installation.
If a chemical product is used, it must be compatible with the installation materials.
Drainage must be made from a low point of the installation, if possible different from the boilers’draining
point.
e2) A separator of oxides and sludge must be installed in the circuits’return, so that all the return water flow
can pass through it, allowing its draining without suspending the service.
Apply the considerations of paragraphs “a,b,c,d”.
If the circuit is in very bad conditions and the previous measures taken were not sufficient, or the cleaning of
the installation was not efficient, the solution would be to separate the boilers’circuit from the heat
emitters’circuit, so that they are independent one from the other, by means of a plate heat exchanger or
similar, according to the hydraulic diagrams included in this manual (see the corresponding paragraph).
ADISA HEATING by HITECSA (HIPLUS)
disposes of professional staff that, after a visit of the installation, can
advise you according to each case.
RECOMENDATIONS:
Only the following quality products for water treatment are allowed:
All these products have to be used strictly in accordance with the water treatment manufacturers’
instructions. Take into account the requirements of the othr parts in the installation
Fernox
- Cleaner F3 : Removes corrosion, lime and sludge
- Protector F1 : Protects against corrosion, lime and sludge
- Alphi-11 : Anti-freeze and protection against corrosion and lime
Sentinel
- X 100: Inhibitor general protection
- X 200: Noise reducer
- X 300: System cleaner for new installations
- X 400: System restorer cleaning of sludge for old installations
- X 500: Inhibited anti-freeze and general protection
Clariant:
-Antifrogen-L: Anti-freeze (mono ethylene glycol) (Note: Antifrogen –N is toxic, it is advised to use
Antifrogen-L)
ADISA HEATING BY HITECSA dispone de personal capacitado para asesorarles según cada caso, previa visita a
la instalación.
Summary of Contents for NEO FIRE 120
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Page 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Page 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Page 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Page 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Page 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Page 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Page 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Page 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Page 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Page 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...