NEO FIRE – Technical Manual
69
18.3
General Maintenance and combustion check
After cleaning burner and heat exchanger check the following:
Check that there is no obstruction on air inlet, siphon or flues.
Check the safeties of the boiler
Air presostat
Minim gas presostat
Water presostat
Ionization electrode
Check that theres is no gas, water or flues leaks when boiler is in operation
Do the gas adjustment (paragraph 17.4.1) and refill a combustion sheet and check that the values are correct.