NEO FIRE – Technical Manual
51
16.7.3
Hydraulic pressure drop
The boiler pressure drop depends on the water flow; the maximum ∆T must be 25 ºC:
If you have to stop the boiler pump, it is required that you stop it with a time delay of 3 to 5 minutes once the
boiler has stopped. This can be obtained by installing a timer-disconnect electrical relay.
Pressure drop NEO FIRE 80-280
Nominal ΔT is 20ºC
Maximum ΔT is 25ºC
Flowrate higher than max indicated can damage the heat exchanger
FLOWRATE at maximum power [m
3
/h]
NEO FIRE
80
120 160 200 240 280
nominal
3,44 5,16 6,87 8,59 10,3 12
min
2,75 4,12 5,5 6,87 8,25 9,62
max
6,8 10,3 13,6 16,4 19,1 21,8