NEO FIRE – Technical Manual
71
19
ECODESIGN DIRECTIVE (ErP)
Model: NEO FIRE
Condensing boiler
CONCEPT
Uts.
80
120
160
200
240
280
360
Power
output
100% (*)
kW
78,0
117,0
156,0
195,0
234,0
273,0
350,5
30% (**)
kW
15,1
22,6
30,2
37,7
45,3
52,8
59,5
Efficiency vs
HCV
100% (*)
%
88,24%
88,25%
88,26%
88,28%
88,29%
88,30%
88,11%
30% (**)
%
97,85%
97,79%
97,72%
97,66%
97,60%
97,53%
98,04%
Efficiency vs
LCV
100% (*)
%
97,61%
97,62%
97,64%
97,65%
97,67%
97,68%
97,47%
30% (**)
%
108,24% 108,17% 108,10% 108,03% 107,96% 107,89% 108,45%
Electrical
Consumption
Operation
at
maximum
power
W
182
168
234
314
408
513
712
Operation
at partial
load
W
39
36
47
59
70
81
93
Stand-by
W
5
5
5
5
5
5
5
NO x
Operation
at
maximum
power
mg/kWh
38
41
44
47
50
52
54
(*): Average Temperature (flow - return): 70ºC
(**): Low temperature is referred to a return temperature of 30 °C for the boilers
See more data in Paragraph 6
Summary of Contents for NEO FIRE 120
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Page 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Page 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Page 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Page 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Page 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Page 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Page 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Page 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Page 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Page 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...