Problem

Possible Causes

Action to take

Inverter is not starting when connected 
to the mains voltage supply

1. Line cord plug is loose.
2. Breaker is broken.
3. Wall socket is damaged.

1. Check the line cord plug.
2. Replace the breaker.
3. Check wall socket with a lamp

.

Output voltage is present,
inverter emits continuous beep sound, 
the yellow LED flashes every 0.5 seconds

Inverter is overloaded

Turn off inverter and unplug excessive loads.

Inverter emits beep sound, battery 
capacity indicator flickers

Low battery

1. Charge batteries.
2. Replace batteries.
3. Call the service.

Inverter does not provide expected 
backup time

1.Excessive loads connected.
2.Battery is weak and cannot 
provide enough energy.

Do not draw any current from the inverter. Leave the
the device plugged in to the mains voltage for 10 
hours. Then test it again. If inverter still can not provide 
expected backup time, battery should be replaced.

Button on front panel does not work

1.The CPU inside inverter
is not running correctly.
2.Button is damaged.

Unplug line cord and battery terminals from the 
inverter to let it shut down automatically. Then, plug in 
line cord and battery again. If the button still fails, 
please call the service.

Inverter cannot turn on the battery mode

1. Battery polarity is wrong.
2. Battery is overcharged.
3. Battery is discharged.
4. Inverter fault.

1. Check battery and connections.
2. Check battery voltage using a voltmeter.
3. Connect the inverter to mains voltage and charge
the battery.
4. Call the service.

1

4

MODEL: 

CO-SinusUPS-600W-LCD

U

SER

 M

ANUAL

Please read and save this manual!

This manual is an important instruction that you should follow during

installation and maintenance of the inverter. Please read all instructions

before using the equipment and save this document for future reference.

CO-sinusUPS-600W-LCD-manual-R3, 20.03.10

6. S

PECIFICATION

Output Power

600VA/500W, 800VA/600W,

950VA/800W, 1200VA/1000W

Input Voltage range/ Frequency

145 ÷ 270VAC ± 5VAC (UPS mode)
100 ÷ 290VAC ± 5VAC (Inverter mode)/ 45 ÷ 65Hz

Output Voltage Range (AC mode)

203VAC ÷ 238VAC ± 5VAC (UPS mode)
150VAC ÷ 255VAC ± 5VAC (Inverter mode)

Output Voltage and Frequency (Battery mode)

220 ± 5VAC, 50Hz ± 0.5Hz

Transfer Time

max. 10ms

Battery Voltage

12VDC or 24VDC

Charging Current

10A/20A (selecetable)

Output Waveform (Battery mode)

Sine Wave

Operation Temperature

0 ÷ 40°C 

Operation Humidity

20 ÷ 90%

Unit dimension

290 x 257 x 123mm

Net weight

10.8kg

7.TROUBLESHOOTING

PURE SINE WAVE INVERTER UPS

A

PPLICATIONS

:

 Central heating and hot water systems, 

Off-grid solar systems, home electronics, WI-FI, 

yachts, campers etc.

CO-sinusUPS-500W/xxx-LCD
CO-sinusUPS-600W/xxx-LCD
CO-sinusUPS-800W/xxx-LCD
CO-sinusUPS-1000W/xxx-LCD
xxx = 12V,24V

Summary of Contents for CO-sinusUPS-500W/LCD Series

Page 1: ...tery mode 1 Battery polarity is wrong 2 Battery is overcharged 3 Battery is discharged 4 Inverter fault 1 Check battery and connections 2 Check battery voltage using a voltmeter 3 Connect the inverter to mains voltage and charge the battery 4 Call the service 1 4 MODEL CO SinusUPS 600W LCD USER MANUAL Please read and save this manual This manual is an important instruction that you should follow d...

Page 2: ... the batteries use the same number and the same type of batteries Overload short circuit over temperature protection Isolation between battery and AC circuitry Good dynamic performance Speed control of cooling fan Front panel Input voltage Output voltage Confirm button Battery type selection Charging current selection Charging current Mode selection ON OFF switch Battery type indicator Battery cab...

Page 3: ...su pracy należy wymienić baterię Przyciski na przednim panelu nie działają 1 Uszkodzenie mikrokontrolera 2 Uszkodzone przyciski Odłącz a następnie podłącz ponownie przewód sieciowy oraz akumulator Jeśli przyciski nadal nie działają skontaktuj się z serwisem Urządzenie nie przechodzi w tryb bateryjny 1 Niepoprawna polaryzacja akumulatora 2 Akumulator przeładowany 3 Akumulator rozładowany 4 Uszkodze...

Page 4: ...cja pomiędzy baterią a wyjściem AC Dobre właściwości dynamiczne Kontrola prędkości wentylatora 4 OBSŁUGA Procedura podłaczenia akumulatora Użyj odpowiedniego akumulatora 12V Podłącz czerwony przewód do dodatniego zacisku i czarny przewód do ujemnego zacisku wejścia akumulatorowego Iskrzenie podczas podłączenia akumulatora jest normalnym zjawiskiem Obsługa Naciśnij POWER przez 3 sekundy żeby włączy...

Reviews: