3-32 Initialization & Installation
(SafeC)
@Example
User command:
~063<CR>
Response:
!061123F0<CR>
06
Address ID
1
Host watchdog timer is enable.
12
Timeout value. 0x12 = 18
18 * 53.3 = 959 ms (Firmware Version 1.x)
18 * 100 = 1800 ms (Firmware Version 2.x)
3F0
0x3F0 is hexadecimal
Analog output value is
4.923 mA
for 0-20mA
Analog output value is
4.923 mA
for 4-20mA
Analog output value is
2.462 V
for 0-10 V
User command:
~063<CR>
Response:
!06112800800800800<CR>
06
Address ID
1
Host watchdog timer is enable.
12
Timeout value. 0x12 = 18
18 * 53.3 = 959 ms (Firmware Version 1.x)
18 * 100 = 1800 ms (Firmware Version 2.x)
800
800
800
800
0x800 is hexadecimal
Analog output value is
0V
for port A
Analog output value is
0V
for port B
Analog output value is
0V
for port C
Analog output value is
0V
for port D