Total Access 3000 Hi-Cap RT Solution Installation and Maintenance Manual
22
64192MB3K2LX-1B
Alarm inputs must be jumpered by the customer to customer-designated and Total Access
3000 input terminals. The customer has the option of determining jumper arrangement and
connection preferences. See
for alarm block connections from each shelf unit
backplane connector to alarm block wire-wrap termination.
Note: “Reporting” connections are used to report alarms to network. “Alarming” connections are to be cross
connected as needed and noted on the Alarm Block label.
Table 8. Alarm Block Terminations
Reporting
Alarming
Total Access 3000 Inputs
Rectifier
Total Access 3000
Shelf 1
RMT
Reporting-1
Power Major
Alarming-1
AUX1
Reporting-2
Power Minor
Alarming-2
AUX2
Reporting-3
AC Fail
Alarming-3
Total Access 3000
Shelf 2
RMT
Reporting-4
Battery on Discharge
Alarming-4
AUX1
Reporting-5
LVD
Alarming-5
AUX2
Reporting-6
Fuse Fail
Alarming-6
Cabinet
ECC Alarm
Alarming-7
Door Intrusion
Alarming-8
Total Access 3000 Fan Module
Fan Fail
Alarming-9