The actual wiring scheme for connecting the shelf to the DSX-1 cross connect is given
in the Application Guide for each of the above applications.
To connect the shelf to a standard DSX-1 cross connect, use 24 AWG, 28-pair/22-pair
twisted, shielded transmission cables with 64-pin/50-pin female connectors on the
shelf end. Two such cables are required for each group of 28/22 connections to the
cross connect.
Table 1. DSX-1 Connections
Total Access Platform
DSX-1 Cross-Connect Positions
TDM Application
Total Access 3000
Total Access 3010
Standard DSX-Fed (APP-301)
56
44
HDSL/T1 DSX-Fed (APP-302)
28
22
DSL Mode DSX-Fed (APP-305)
28
22
QFO-C only DSX-Fed (APP-306)
56
44
Standard Combo-Fed (APP-307)
56
44
HDSL/T1 only Combo-Fed (APP-308)
28
22
DSL Mode Combo-Fed (APP-309)
28
22