6TANTP505-1E
TOTAL ACCESS 3000/3010
NTP-505
Page 3 of 4
Total Access
®
3000/3010 System Manual
© 2003, ADTRAN, Inc.
1.3.2
Install the Primary STS-1 MUX
1. Gently but firmly push the STS-1 MUX into the second slot, slot A, at the left
end of the shelf. Simultaneous thumb pressure at the top (above the POWER
LED) and bottom (below the Test/Enable button) of the unit will ensure a
good seat of the STS-1 pins into the backplane connector. Push the ejector tab
up and closed against the STS-1 faceplate.
2. Allow the unit approximately 30 seconds to completely power up and synchronize
with the SCU. Upon completion, the POWER LED will be FLASHING yellow,
indicating and Out-of-Service, unassigned (OOS-UA) state and the ON LINE
LED will be off. The ONLINE LED will remain off until the unit is placed in the
In-Service state and becomes the service provider to the network. Also, the
STATUS LED will be red and the CLOCK LED will be yellow if the receive
STS-1 signal is not present. No alarms will be passed on to the network until the
unit is placed in the In-Service state.
3. If a single configuration is being employed, proceed to
provision the STS-1 MUX module. If a protection configuration is being
employed, proceed to DLP-741 after the Protect MUX module has been installed.
1.4 Protect MUX (slot B) Installation Procedure
1.4.1 Unpack and Inspect the Protect STS-1 MUX Module
Each STS-1 MUX module is shipped in its own cardboard shipping carton. Open the
carton carefully and avoid deep penetration into the carton with sharp objects. After
removing the unit from the carton, unwrap the bubble-wrap and pull the unit from the
antistatic plastic bag.
Inspect it for possible shipping damage. If the equipment has damaged in transit, file a
claim with the carrier, then contact ADTRAN Customer Service.
1.4.2 Install the Protect STS-1 MUX
1. Gently but firmly push the STS-1 MUX into the third slot, slot B, at the left end of
the shelf. Simultaneous thumb pressure at the top (above the POWER LED) and
bottom (below the Test/Enable button) of the unit will ensure a good seat of the
STS-1 pins into the backplane connector. Push the ejector tab up and closed
against the STS-1 faceplate.
2. Allow the unit approximately 30 seconds to completely power up and synchronize
with the SCU. Upon completion, the POWER LED will be FLASHING yellow,
indicating and Out-of-Service, Unassigned (OOS-UA) state and the ON LINE
LED will be off. The ONLINE LED will remain off until the unit is placed in the
In-Service state and becomes the service provider to the network. Also, the
STATUS LED will be red and the CLOCK LED will be yellow if the receive ST
signal is not present. No alarms will be passed on to the network until the unit is
placed in the In-Service state.
3. Proceed to DLP-741 for procedure to provision the STS-1 MUX modules.