Total Access
®
3000/3010 System Manual
6TADLP710-1E
TOTAL ACCESS 3000/3010
DLP-710
Page 1 of 4
© 2002, ADTRAN, Inc.
Perform Steps Below in the Order Listed
1.1
Connecting the External Alarm Outputs
NOTE
References to common, but differing, parameters between the Total Access
3000 and the Total Access 3010, such as number of slots, will be conveyed
by the convention a/b. The “a” represents the Total Access 3000 parameter
and the “b” represents the Total Access 3010 parameter. For example, the
differing number of access slots in the two platforms, 28 for the Total Access
3000 and 22 for the Total Access 3010, would be displayed “28/22.”
1.1.1
Introduction
This DLP explains how to connect external alarm outputs to Total Access 3000/3010.
1.1.2
Prerequisite Procedures
Before making external alarm connections, the Total Access 3000/3010 shelf should
be mounted in its permanent location in the CO.
1.1.3
Tools and Materials Required
• Wire strippers
• Wire-wrap gun
• 22 or 24 AWG 2-conductor twisted pair cross connect wire
WARNING
To prevent electrical shock, do not install equipment in a wet location or
during a lightning storm.
CAUTION
Electronic modules can be damaged by static electrical discharge. Before
handling modules, wear an antistatic discharge wrist strap to prevent damage
to electronic components. Place modules in antistatic packing material when
transporting or storing. When working on modules, always place them on an
approved antistatic mat that is electrically grounded.