Perform Steps Below in the Order Listed
1.2
Detailed Level Procedure 714
1.
Connect the DB-25 data cable male connector to the NTWK MGMT port,
J30/J17, on the Total Access 3000/3010 backplane.
2.
Connect the other end of the data cable to the designated port of the X.25
switch. See Table 1 for the pinout of the NTWK MGMT port.
3. Configure the port on the X.25 switch per Table 2.
NOTE
The CO X.25 network administrator must configure the X.25 switch for the
Total Access 3000/3010 shelf, accomplishing tasks such as assignment of an
LDN number for the shelf.
NOTE
It is possible to remote the X.25 interface over a DDS line of up to 64 Kbps
capacity, with the network designer designing the specific interface. Some
smaller COs without an X.25 switch may desire to take advantage of this
capability.
1.2.1
Followup Procedures
Once this procedure is complete, return to the procedure which called out this DLP and
continue with the tasks indicated there.
CAUTION
Electronic modules can be damaged by static electrical discharge. Before
handling modules, wear an antistatic discharge wrist strap to prevent damage
to electronic components. Place modules in antistatic packing material when
transporting or storing. When working on modules, always place them on an
approved antistatic mat that is electrically grounded.