6TADLP742-1E
TOTAL ACCESS 3000/3010
DLP-742
Page 6 of 14
© 2003, ADTRAN, Inc.
Total Access
®
3000/3010 System Manual
Perform Steps Below in the Order Listed
10. Selecting option,
Restore Factory Defaults
, will restore the provisioning of the unit
to its factory default state. The factory default settings are listed below:
Service State:
Out-of-Service, Unassigned
Linked Provisioning:
Enable
Signal Fail Threshold:
1x10-3
Signal Degrade Threshold:
1x10-5
Clock Source:
Receive OC-3 A&B
OC-3 TX sync msg:
Derive from Source
DCC Side:
Network
Clk Out Type:
DS-1 SF
Clk out LBO:
000-133 feet
Clk out Enable:
Disabled
Clk output:
Dual Output
Clk Out Source:
Receive OC-3
PM Threshold:
Disabled
VT Mapping:
Unmapped
11. Return to the Primary MUX Main Menu by pressing <Esc> and proceed to the
next section.
1.4
Performance Monitoring Provisioning
Performance monitoring options can be set to enable the module to capture
performance monitoring data. Alarm thresholds for various alarm conditions are set
and, when exceeded, issue an appropriate alarm. To set alarm threshold values perform
the following.
1. From the Primary MUX Main Menu select option 6,
Performance Monitoring
, and
press <Enter>.