6TADLP742-1E
TOTAL ACCESS 3000/3010
DLP-742
Page 8 of 14
© 2003, ADTRAN, Inc.
Total Access
®
3000/3010 System Manual
Perform Steps Below in the Order Listed
5. From the Performance Monitoring Menu select option 6,
OC-3 Quarterly Hourly
Thresholds
, and press <Enter>.
1.
Section Code Violations
2.
Section Errored Seconds
3.
Section Severely Errored Seconds
4.
Line Code Violations
5.
Line Errored Seconds
6.
Line Severely Errored Seconds
7.
Line Unavailable Seconds
8.
Path Code Violations
9.
Path Errored Seconds
10.
Path Severely Errored Seconds
11.
Path Unavailable Seconds
6. For an example, from the Quarterly Hourly Threshold Menu select option 9,
Path
Errored Seconds
, and press <Enter>.
1.
Set Alarm Threshold
125
2.
Set Alarm Enable
Disabled
Set the Alarm Threshold by selecting option 1,
Set Alarm Threshold
, and inputting the
desired threshold. Finally, enable the alarm by selecting option 2, Set Alarm Enable,
and setting to Enable. This will cause that alarm to be issued if the set threshold value
is exceeded.
7. Return to the Primary MUX Main Menu by pressing <Esc> and proceed to the
next section.