Total Access
®
3000/3010 System Manual
6TADLP744-1E
TOTAL ACCESS 3000/3010
DLP-744
Page 4 of 12
© 2003, ADTRAN, Inc.
Perform Steps Below in the Order Listed
4.) Connect the other end of this cable to the female BNC connector labeled TX
on the Dual BNC Adapter Module that is installed on the rear of the first
Expansion Shelf.
5.) Use a BNC ended male-to-male high speed cable of proper length to connect
to the female BNC connector labeled TX on port 2 (located closest to the aisle)
on the Quad BNC Adapter Module that is installed on the rear of the
Intelligent NE (Host) shelf.
6.) Connect the other end of this cable to the female BNC connector labeled RX
on the Dual BNC Adapter Module that is installed on the rear of the second
Expansion Shelf.
7.) Use a BNC ended male-to-male high speed cable of proper length to connect
to the female BNC connector labeled RX on port 2 (located closest to the aisle)
on the Quad BNC Adapter Module that is installed on the rear of the
Intelligent NE (Host) shelf.
8.) Connect the other end of this cable to the female BNC connector labeled TX
on the Dual BNC Adapter Module that is installed on the rear of the second
Expansion Shelf.
4.
Verify Common Modules Installed in Intelligent NE and Expansion
Shelves
1.) Verify that the SCU, ADTRAN P/N 1181018L1 and either single or redundant
OC-3 List 2 MUX Modules, ADTRAN P/N 1181031L2 are installed in the
Intelligent NE (Host) shelf.
2.) Verify that the SCU, ADTRAN P/N 1181018L1 and either single or redundant
STS-1 List 2 MUX Modules, ADTRAN P/N 1181030L2 are installed in all
Expansion Shelves (Client).
5.
Verify RS-485 Bus Connection
1.) Verify that DLP-712 (part of NTP-501) has been completed. Pins A, B, and
Drain/Ground “OUT” on wire-wrap header P2 on the rear of the Intelligent NE
(Host) shelf should be connected to pins A, B, and Drain/Ground “IN” on
wire-wrap header P2 on the rear of the first Expansion Shelf (Client). Pins A,
B, and Drain/Ground “OUT” on wire-wrap header P2 on the rear of the first
Expansion Shelf (Client) should be connected to pins A, B, and Drain/Ground
“IN” on wire-wrap header P2 on the rear of the second Expansion Shelf
(Client).