6TANTP501-1E
TOTAL ACCESS 3000/3010
NTP-501
Page 1 of 22
Total Access
®
3000/3010 System Manual
© 2002, ADTRAN, Inc.
1.1
23"/19" Shelf Installation in a Central Office (CO),
Multi-Tenant Unit (MTU) or Remote Terminal (RT)
1.1.1
Introduction
This section provides step-by-step instructions for the installation of one or more Total
Access 3000 or Total Access 3010 (Total Access 3000/3010) shelves in a Central
Office (CO). Installation procedures include the removal of the Total Access 3000/
3010 shelves from shipping containers, mounting shelves in a CO rack, power up, all
necessary data and administrative connections, and turnup. Acceptance testing is
provided in section 6, (Acceptance Test Procedure, ATP-601) of this system manual.
NOTE
References to common, but differing, parameters between the Total Access
3000 and the Total Access 3010, such as number of slots, will be conveyed
by the convention a/b. The “a” represents the Total Access 3000 parameter
and the “b” represents the Total Access 3010 parameter. For example, the
differing number of access slots in the two platforms, 28 for the Total Access
3000 and 22 for the Total Access 3010, would be displayed “28/22.”
1.1.2
Prerequisite Procedures
Before beginning the installation described in this NTP, the installer should thoroughly
review the document
Preparing for Shelf Installation
PREP-401, in section 4 (Site
Preparation) of this systems manual. Based on PREP-401, the installer will know
which steps of this NTP will be required for the intended use of the Total Access 3000/
3010 shelf.
To comply with UL1950 requirements, the following steps must be adhered to:
•
Connect to a reliably grounded -48 VDC source which is electrically isolated from
the AC source.
•
A readily accessible disconnect device, that is suitably approved and rated, shall be
incorporated in the fixed wiring.
•
The branch circuit overcurrent protection shall be a fuse or circuit breaker rated
-48 VDC minimum, 30A maximum.
•
This product is intended for installation in Restricted Access Locations Only.
•
This unit shall be installed in accordance with the requirements of NEC NFPA 70.
•
Instructions stating the proper methods for grounding shall be included within the
guidelines of the installation practice.