6TANTP504-1E
TOTAL ACCESS 3000/3010
NTP-504
Page 1 of 4
Total Access
®
3000/3010 System Manual
© 2003, ADTRAN, Inc.
1.1
Total Access 3000/3010 DS3 MUX Installation in a Central
Office Shelf
NOTE
References to common, but differing, parameters between the Total Access
3000 and the Total Access 3010, such as number of slots, will be conveyed by
the convention a/b. The “a” represents the Total Access 3000 parameter and the
“b” represents the Total Access 3010 parameter. For example, the differing
number of access slots in the two platforms, 28 for the Total Access 3000 and
22 for the Total Access 3010, would be displayed “28/22.”
1.1.1
Introduction
This procedure provides step-by-step instructions for the installation of the Total
Access 3000/3010 DS3 MUX Module into a Total Access 3000/3010 Central Office
shelf. Installation procedures include the removal of the product from its packaging,
inspecting for damage and seating the unit in the shelf. Acceptance testing is provided
in section 6 (Acceptance Test Procedure, ATP-601) of this system manual.
1.1.2
Prerequisite Procedures
The following procedures must be completed prior to installing the DS3 MUX module.
If necessary, refer to the appropriate documentation before proceeding. The
prerequisite procedures include:
• Installation and wiring of Total Access 3000/3010 shelf and SCU – NTP-501
• BNC module installation – DLP-708
• Coaxial cable installation – PREP-401, DLP-709
1.1.3
Materials Required
• Total Access 3000/3010 DS3 MUX module (two modules for 1:1 protection
switching applications)
1.2
First-time MUX Installation
CAUTION
Electronic modules can be damaged by static electrical discharge. Before
handling modules, wear an anti-static discharge wrist strap to prevent damage
to electronic components. Place modules in anti-static packing material when
transporting or storing. When working on modules, always place them on an
approved anti-static mat that is electrically grounded.