Total Access
®
3000/3010 System Manual
6TADLP717-1E
TOTAL ACCESS 3000/3010
DLP-717
Page 1 of 4
© 2002, ADTRAN, Inc.
Perform Steps Below in the Order Listed
1.1
Setting TIRKS Parameters in the SCU
NOTE
References to common, but differing, parameters between the Total Access
3000 and the Total Access 3010, such as number of slots, will be conveyed
by the convention a/b. The “a” represents the Total Access 3000 parameter
and the “b” represents the Total Access 3010 parameter. For example, the
differing number of access slots in the two platforms, 28 for the Total Access
3000 and 22 for the Total Access 3010, would be displayed “28/22.”
1.1.1
Introduction
Remote management systems require a specific address and description for every
system they manage. The Target ID (TID) and Shelf Number must be registered with
the management system before it can find and manage Total Access 3000/3010. This
procedure assigns the codes to the Total Access 3000/3010 shelf for use with the
management system.
NOTE
For up to 32 Total Access 3000/3010 shelves to operate on a daisy chain
connected by the RS-485 bus, all the shelves on the chain must have a
unique Shelf Number to identify the specific shelf on the chain. More
detailed information about the RS-485 is located in DLP-712, and
NTP-501 of this system manual.
NOTE
The Target ID (TID) and the Shelf Number will be issued from the TIRKS
system and should be provided to the installer as part of the Total Access 3000/
3010 installation package. If not, see the CO system administrator for Target
ID (TID) and Shelf Number assignment. For COs not using TIRKS, values
must still be put into the Target ID (TID) and Shelf Number locations if the
shelf is to be used as a host or client shelf on the RS-485 bus.
1.1.2
Prerequisite Procedures
You must be connected and logged on to set the TIRKS parameters in the SCU.
1.1.3
Tools and Materials Required
• Data cable to connect to VT100 terminal or PC configured as a VT100 terminal
• VT100 or PC configured as a VT100 terminal