background image

0160_IOM_1.2_Mar21_5

5

Nom. duct width

Opening width min.

Opening width max.

100-1,000mm

Nom. duct +194mm

Nom. duct +350mm

Nom. duct height Opening height min. Opening height max.

100mm

Nom. duct +100mm

Nom. duct +350mm

101-300mm

Nom. duct +125mm

Nom. duct +375mm

301-525mm

Nom. duct +150mm

Nom. duct +400mm

526-700mm

Nom. duct +175mm

Nom. duct +425mm

701-925mm

Nom. duct +200mm

Nom. duct +450mm

926-1,000mm

Nom. duct +225mm

Nom. duct +475mm

FIRE – 0160 ADJUSTABLE FRAME SYSTEM (IN WALL) FOR TWO HOUR FLEXIBLE SUPPORTING CONSTRUCTION

Preparation

 Ensure that the damper is kept 

in a clean dry environment and 

that there is no damage to the 

damper.

 Remove all the packaging and 

transit ties before installation.

 Work out the opening size to be 

cut using the adjacent table.

Patented Adjustable Frame System

(AFS) incorporating bracket, bracket

slot, and Z-piece

(Patent No: GB2557865)

Closure face board

Access door for

inspection / damper reset

0160 Series fire damper

Two layers of 50mm thick

140kg/m3 fire batt

M10 drop rods

15mm thick gypsum boards

Two hour rated flexible

supporting construction

to BS EN 1363-1:2020

Steel stud depth –

71 to 100mm

Installation sequence

 The drywall will consist of two layers of 15mm plasterboard each side of steel studwork with an 

optional mineral wool insulation. The opening will be a letterbox construction with overlapping layers 

of plasterboard with an opening clearance around the damper casing in line with the above table.

 Two M10 drop rods per fire damper shall be fitted centrally within the flexible wall fixed by steel anchors 

into the slab or soffit above. These should be securely installed in line with the manufacturer’s fixing 

instructions in a position to match the AFS rail.

 The drop rods should have a nut screwed on for clamping the rail from above.

 Slide the AFS rails on each side of the damper into the brackets and insert the “Z” piece into the 

bracket slot pushing it up against the underside of the rail. Insert the 8mm bolt from above into the slot 

through the “Z” piece fitting the nut until tight to secure the rail.

 The damper should be mounted centrally in the opening as detailed in the drawing. The drop rods 

are to slide through the slots in the rail and a nut screwed on to take the support of the damper rail. 

The damper must then be levelled and when in the correct position the nut above the rail should be 

tightened against the rail.

 The galvanised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm, 

leaving a minimum 10mm clearance for any duct expansion in a fire situation. 

10 

 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild 

steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at 

high temperature allowing the duct to break away without effecting the integrity of the installation.

11 

 The connecting galvanised mild steel ductwork must be independently supported within one metre of 

the connections and have been installed in accordance with DW144.

12 

 The gap between the damper and the wall opening will need filling with two layers of 50mm thick 140kg/m3 

fire batt cut to an interference fit and pushed in to place. All cut edges must be sealed with a firebatt 

sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to each joint.

13 

 A closure face board of 15mm plasterboard is screwed to each side of the of the wall. It must fully cover 

the fire batt and overlap the opening by 50mm.

14 

 An access door should be fitted on the access side of the damper to enable the resetting of the 

damper blades.

15 

 When the damper installation has been completed checks should be made to ensure the drop rods 

are secured to the cleats and there is no movement, operation of the damper should be checked.

16 

 Complete DW145 Fire Damper Certificate.

PRODUCT  

0160 W/ AFS RAIL

APPLICATION  

FLEXIBLE SUPPORTING CONSTRUCTION, SUPPORT IN WALL

CLASSIFICATION REPORT NO.  

BRE 287811C

CLASSIFICATION  

E120 (VE I 



 O)

TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING. 

Summary of Contents for 0160 Series

Page 1: ...0160_IOM_1 2_Mar21_1 1 MODEL 0160 FIRE DAMPER AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Page 2: ...all AFS with drop rods in wall 5 Two hour flexible wall multi section AFS with drop rods two sides 6 Two hour rigid wall AFS with drop rods one side 7 Two hour rigid wall HEVAC 8 Two hour flexible wal...

Page 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...for any duct expansion in a fire situation 10 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fixed with low resistance fixings...

Page 5: ...to the slot through the Z piece fitting the nut until tight to secure the rail 8 The damper should be mounted centrally in the opening as detailed in the drawing The drop rods are to slide through the...

Page 6: ...ork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at high temperature allowing the duct to break away without effecting the integrity of the installation 12 The...

Page 7: ...et slot pushing it up against the underside of the rail Insert the 8mm bolt from above into the slot through the Z piece fitting the nut until tight to secure the rail 7 The damper should be centrally...

Page 8: ...ture allowing the duct to break away with affecting the integrity of the installation 11 The connecting galvanised mild steel ductwork must be independently supported within one metre of the connectio...

Page 9: ...l ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at high temperature allowing the duct to break away without effecting the integrity of the installation...

Page 10: ...tend past the opening on each side by 100mm 5 Position the dampers evenly in the centre of the opening 6 Secure the angles to the floor Mark the hole positions on the angle at least 50mm away from the...

Page 11: ...nised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm leaving minimum 10mm clearance for any duct expansion in a fire situation 12 The galvanised mild steel ductwork co...

Page 12: ...the blades and spring system 0160 OPERATION AND MAINTENANCE Visually inspect the damper blades to ensure that they are all interlocked that the springs are straight and that the bottom damper is lock...

Page 13: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...

Reviews: