Advanced Air UK Ltd
Burrell Way
Thetford
Norfolk IP24 3QU
Tel: 01842 765657
Email: Projects@advancedair.co.uk
2530 CE Series
Smoke Fire Damper
Due to continuous product development Advanced
(U.K.) Ltd reserves the right to change any
information without prior notice
Date
Issue
Sheet
Spec Number
April 2018
C
3 of 34
TS2530CE-01
G:\PRODUCTS\DMP - 2500 Series\05 Product Data\2530\Tech Sub\2530CE\TS2530CE-01 Technical Sub Rev C.docx
Minimum and maximum permissible duct sizes
As standard, all dampers shall be shipped as single section up a nominal duct size of 1000mm x1000mm.Dampers
larger than this will be shipped as a multi-section damper fixed together at Advanced Air and shipped as one piece.
Dampers larger than 2050mm wide or 2050mm high will be split and shipped as separate pieces, each piece being
no larger than a duct size of 2050mm x 2050mm. Below are the minimum and maximum sizes possible (Available
in 1mm increments).
Duct Size
Rectangular:
Minimum 100mm wide x 100mm high (Case size 250mm x 250mm)
(single-section)
Maximum Single Section 1000mm wide x 1000mm high
Circular:
Minimum 100mm diameter (case size 250mm x 250mm)
Maximum 950mm diameter
Flat Oval:
Minimum 100mm wide x 100mm high (Case size 250mm x 250mm)
Maximum 950mm on longest dimension.
Duct Size
Rectangular:
Maximum multi-section 2050mm wide x 2050mm high
(multi-section
Circular:
Maximum 1500mm Diameter.
shipped on one piece)
Flat Oval:
Maximum 1500mm on longest dimension.
Duct Size
Rectangular:
Maximum multi-section - None stated
*See below
(multi-section
Circular:
Not available
shipped in separate
Flat Oval:
Not available
pieces)
* Further structural support may be required, please consult a Structural Engineer for advice.