background image

0400_IOM_1.

1_Mar21_5

5

PRODUCT  

0400MAN

APPLICATION  

RIGID SUPPORTING CONSTRUCTION

CLASSIFICATION REPORT NO.  

P105424-1003

CLASSIFICATION  

E120 (VE I 



 O)

TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING. 

FIRE – 0400MAN CIRCULAR FIRE DAMPER IN RIGID SUPPORTING CONSTRUCTION

Fire batt

Access door

135mm minimum thickness

two hour rated rigid supporting

construction to BS EN 1363-1:2020

OPEN

CLOSE

Installation sequence

 The damper should be mounted in the opening with the fixing flange (access side) flush with the wall.

 Confirm that the blade is horizontal, and the handle is on the RH or LH. The flange can then be secured 

to the wall using fire resistant steel fixings. Ensure that all the pre-drilled holes are populated.

 The gap between the damper and the wall opening will need filling with two layers of 50mm thick 

140kg/m

3

 fire batt cut to interference fit and pushed into place. All cut edges must be sealed with a 

fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied to 

each joint.

 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm, 

leaving a 10mm clearance for any duct expansion in a fire situation.

 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild 

steel ductwork sealer and fixed with low resistance fixings such as aluminium rivets that will melt at 

high temperature allowing the duct to break away without affecting the integrity of the installation.

 The connecting galvanised mild steel ductwork must be independently supported within one metre of 

the connections and have been installed in accordance with DW144.

An access door should be fitted on the access side of the damper for inspection and maintenance.

10 

When the damper installation is complete the operation of the damper should be checked.

11 

Complete DW145 Fire Damper Certificate.

Preparation

 Ensure the that damper is kept in a clean dry 

environment and that there is no damage to the 

damper.

 Work out the opening size to be cut by adding 

55mm to the duct diameter and cut a square hole to 

that size, see adjacent table.

Nom. duct diameter

Opening size

100mm

155 x 155mm

125mm

180 x 180mm

150mm

205 x 205mm

160mm

215 x 215mm

200mm

255 x 255mm

250mm

305 x 305mm

300mm

355 x 355mm

315mm

370 x 370mm

Summary of Contents for AIR CONTROL 0400FME

Page 1: ...0400_IOM_1 1_Mar21_1 1 AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL MODEL 0400 FIRE DAMPER...

Page 2: ...er Model 0400MAN Two hour flexible wall 4 Two hour rigid wall 5 Circular fire damper Model 0400FME Two hour flexible wall 6 Two hour rigid wall 7 Operation and Maintenance Model 0400MAN 8 Model 0400FM...

Page 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...it and pushed into place All cut edges must be sealed with a fire batt sealant to BS EN 13501 2 A fire rated intumescent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild st...

Page 5: ...l be applied to each joint 6 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvan...

Page 6: ...cent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion...

Page 7: ...30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fix...

Page 8: ...blade may have been incorrectly positioned or the damper may be faulty Please contact Advanced Air for advice Maintenance 0400MAN dampers are installed as a life safety product and it is essential tha...

Page 9: ...ion For other faults contact Advanced Air Sales Office Complete any relevant reports Maintenance 0400FME dampers are installed as a life safety product and it is essential that they are always maintai...

Page 10: ...5 6 7 8 G PRODUCTS DMP 0400 Series 02 Drawings D0400 ES Electrical Schematics D0400 ES001 Wiring diagram fire smoke damper actuator D0400 ES001 rev B Wiring diagram 0400 FME dwg Wiring detail for dam...

Page 11: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...

Reviews:

Related manuals for AIR CONTROL 0400FME