Initial operating check

The 0400FME damper should only be commissioned once it is fully installed and connected to electrical 

power. The damper should be inspected thoroughly to ensure that it is clean and free of any internal debris 

before the damper actuation is tested as per the following instructions:
• 

Isolate the power.

• 

Remove the access door.

• 

 Test the damper manually by using the Allen key provided and 

turning it clockwise until the damper is fully opened, mechanically 

lock the actuator by using a screwdriver to turn the 

STOP SHAFT

 5⁰.

• 

 Visually inspect the damper checking that the damper is in its fully 

opened position.

• 

 Close the damper by turning the Allen key clockwise and releasing 

it, the spring action of the actuator will wind the damper to its fully 

closed position.

• 

 Visually inspect the damper checking that the damper is in its fully 

closed position.

• 

 Reapply power to the actuator. The actuator will start to travel, and 

GREEN

 light will be lit on the Thermal Release housing, it will take 

90 seconds to fully open.

• 

 The switch on the Thermal Release housing can be pressed to 

simulate activation of the thermal release, the LED light will turn 

RED

 and the actuator will spring return to its unpowered position, 

it should take 15 seconds to complete this cycle.

• 

 Release the switch and the damper will return to its fully opened 

position.

• 

 Visually inspect through the access door that the blades are fully 

open and then re-fit the access door.

• 

Damper not fully opening or closing?

 

• 

Obstruction to the blades – remove the obstruction.

 

• 

 Incorrect set up of the actuator – the actuator has been adjusted by others from the Factory Set 

position.

 

• 

For other faults contact Advanced Air Sales Office.

• 

Complete any relevant reports.

Maintenance

0400FME dampers are installed as a life safety product and it is essential that they are always maintained 

so they are in a clean working condition. In accordance with BS9999 Annex W.1 maintenance and inspection 

should be undertaken annually.
Maintain the dampers as follows;
• 

Remove the access door to internally inspect the damper.

• 

 Visually inspect all damper components for signs of corrosion, obstructions and build-up of dirt/dust.

• 

 Remove any obstructions, wipe away all dirt and dust from the damper blades and duct surfaces.

• 

 Check that the thermal release probe is intact and does not show signs of damage.

• 

 After internal inspections are complete a functional check of the damper should be made.

• 

 The 0400FME damper is fitted with an electrical thermal release probe and its housing has a LED light 

and an On/Off toggle switch.  

 

• 

 A 

GREEN

 light indicates that there is a power supply and that the thermo sensor is OK.  

 

• 

 A 

RED

 light indicates a power supply but there is a fault.  

 

• 

No light indicates that there is no power supply.

• 

 Push and hold the toggle switch to simulate over-temperature. This simulates the response of the 

thermal release, enabling the proper functioning test of the actuator and damper. It will take 15 seconds 

for the damper to close and during the test the LED light will turn 

RED

.   

• 

 After checking that the blades on the damper are fully closed, release the switch and the actuator will 

power to its open position and the light will turn 

GREEN

, check the blades are in the open position. 

• 

 Refit the access door and complete maintenance reports as appropriate.

0400FME – OPERATION AND MAINTENANCE

LED Light

RED

 

Operating voltage OK. Thermo sensor defect.

GREEN

 

Operating voltage OK. Thermo sensor OK.

DARK

 

No operating voltage.

STOP SHAFT

 

– turn 5º

Allen key slot

Switch

Summary of Contents for AIR CONTROL 0400FME

Page 1: ...0400_IOM_1 1_Mar21_1 1 AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL MODEL 0400 FIRE DAMPER...

Page 2: ...er Model 0400MAN Two hour flexible wall 4 Two hour rigid wall 5 Circular fire damper Model 0400FME Two hour flexible wall 6 Two hour rigid wall 7 Operation and Maintenance Model 0400MAN 8 Model 0400FM...

Page 3: ...luded within this manual an example of the Fire Damper Certificate DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...it and pushed into place All cut edges must be sealed with a fire batt sealant to BS EN 13501 2 A fire rated intumescent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild st...

Page 5: ...l be applied to each joint 6 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvan...

Page 6: ...cent mastic to BS EN 13501 2 shall be applied to each joint 7 The galvanised mild steel ductwork connecting to the damper spigots should overlap by 30mm leaving a 10mm clearance for any duct expansion...

Page 7: ...30mm leaving a 10mm clearance for any duct expansion in a fire situation 7 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild steel ductwork sealer and fix...

Page 8: ...blade may have been incorrectly positioned or the damper may be faulty Please contact Advanced Air for advice Maintenance 0400MAN dampers are installed as a life safety product and it is essential tha...

Page 9: ...ion For other faults contact Advanced Air Sales Office Complete any relevant reports Maintenance 0400FME dampers are installed as a life safety product and it is essential that they are always maintai...

Page 10: ...5 6 7 8 G PRODUCTS DMP 0400 Series 02 Drawings D0400 ES Electrical Schematics D0400 ES001 Wiring diagram fire smoke damper actuator D0400 ES001 rev B Wiring diagram 0400 FME dwg Wiring detail for dam...

Page 11: ...o damper also through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the in...

Reviews: