background image

1314-900 Revision BA 

250W Precision Calorimeter

 

flow (gm/sec) and specific heat of the transfer medium cp (J/gm-°C): 

Watts = J/sec = m

ass flow rate (gm/sec) x ΔT (°C) x specific heat (J/gm

-

°C)

 

The system design utilizes the absolute flow method which means it measures the absolute flow 
within the system keeping it nearly constant in order to determine ΔT. A basic absolute flow 
calorimeter system in general is typically comprised of a liquid cooled RF load with a closely 
coupled thermopile, circulating pump/heat exchanger, and signal conditioning circuits with a 
display. The 1314 block diagram is shown in Figure 2. To begin, RF energy is converted to heat 
energy inside a RF load containing a circulating coolant flow. The heat energy is dissipated in the 
coolant, carrying this heat away in the coolant. The fluid circuitry causes the coolant to come in 
contact with the heat sensing surfaces of a closely coupled thermopile located between the load 
coolant inlet and outlet and thereby senses the temperature rise across the coolant and produces a 
DC voltage. The resultant voltage is not proportional to the absolute temperature of the coolant 
but to the difference in temperatures of the coolant streams. The entire heated coolant stream is 
involved in the measurement, not just a fraction. Since temperature is read out as a difference 
(rather than an absolute quantity) within the thermopile, the only absolute measurement required 
is the rate of flow made by the flow meter- and this can be made reasonably accurately. More 
importantly, if the flow meter is highly repeatable, the minor absolute flow measurement errors 
can be calibrated out with extreme accuracy. A chiller then removes the heat picked up by the 
fluid and exhausts it to the ambient air. The cooled fluid is then recirculated back to the load in a 
closed loop. The DC voltage from the thermopile and the flow meter output pulses are fed into a 
signal conditioning board and then on to a display, calibrated in RF watts (also available on the 
remote computer interface for automated system configurations). Thermistors are utilized on both 
the input and output water pipes to sense the absolute temperatures of the water stream at their 
respective points and are then used to compensate for errors introduced in the specific heat and 
gravity characteristics of the system fluid as a function of temperature. To allow for some 
variability in the flow rate for the system, an adjustable flow valve is made available, and is 
inserted in series with a fluid line connecting the inlet stream directly to the outlet stream. This 
valve is normally set to produce a flow rate of .5 GPM for the system, as this is the recommended 
minimum flow rate required by the RF load to achieve the system specification of 250 watts. 

Summary of Contents for 1314

Page 1: ...250W Model 1314 Precision Calorimeter User Manual February 2023 1314 900 Revision BA...

Page 2: ...nformation contained herein Product Usage Statement WARNING READ THIS ENTIRE MANUAL AND ALL OTHER PUBLICATIONS PERTAINING TO THE WORK TO BE PERFORMED BEFORE YOU INSTALL OPERATE OR MAINTAIN THIS EQUIPM...

Page 3: ...ergy s technical writing staff has carefully developed this manual using research based document design principles However improvement is ongoing and the writing staff welcomes and appreciates custome...

Page 4: ...e Location Where the Unit Will Be Installed 9 Fill the Coolant Reservoir 9 Establish Communication with the 1314 10 Connect the Chiller and Prime the Coolant Pump 12 Adjusting Coolant Flow 15 Adjustin...

Page 5: ...er v Appendix A 27 Appendix B Service Assistance 28 Returns for Repairs 28 Warranty 28 Warranty Limitations 29 Statement of Calibration 29 Storage and Shipment 30 Drain the calorimeter system of all c...

Page 6: ...ot designed for operation in explosive environments WARNING DO NOT OPERATE WITHOUT COVERS This device should be operated with all panels and covers in place Operation with missing panels or covers cou...

Page 7: ...practices or tips for efficiency Terms on Equipment CAUTION indicates a personal injury hazard not immediately accessible as one reads the marking or a hazard to property including the equipment itse...

Page 8: ...A4 AC Power Standard optional 100 240 VAC 10A4 Physical Dimensions Approximate Calorimeter 4 height 19 width 23 depth not in optional rack Chiller 7 height 19 width 28 depth not in optional rack AC Po...

Page 9: ...options 1 Average of ten 10 consecutive points taken 25 seconds apart where the standard deviation of those points is 0 05 W 2 The 1314 is intended for use as a primary standard Measurement repeatabi...

Page 10: ...en conversely if we know the temperature rise and the mass of the liquid we can determine the amount of heat and therefore the amount of energy applied to the liquid The calorimeter utilizes these fun...

Page 11: ...Since temperature is read out as a difference rather than an absolute quantity within the thermopile the only absolute measurement required is the rate of flow made by the flow meter and this can be m...

Page 12: ...1314 900 Revision BA 250W Precision Calorimeter 7 Figure 3 Block Diagram Figure 4 Signal Processing Block Diagram...

Page 13: ...arton for the following items Table 1 Packing List Item Part Number Model 1314 Precision Calorimeter 1314 300 Technical Operation and Maintenance Manual 1314 840 CD or 1314 900 Printed Chiller 1314 38...

Page 14: ...e intake and outlet gratings on the rack are important Notice the red and blue arrows depicting air flow in Figure 4 below Figure 5 Airflow 3 Lock caster wheels once location is determined Fill the Co...

Page 15: ...O NOT USE AUTOMOTIVE COOLANT Automotive coolant uses unknown and or inadequate corrosion protection systems that may be incompatible with materials in your calorimeter 4 Add a drop of ordinary dishwat...

Page 16: ...14 is ready for further commands it will display a power measurement value and a frequency setting value It will be necessary to find the Ethernet address assigned to the unit under the softkey setup...

Page 17: ...flow present The flowrate should display 0 as there is no fluid present and the pump has not been turned on yet This flowrate value will guide you to establishing the proper flowrate once the pump ha...

Page 18: ...ed excess air back into the reservoir without intervention 6 When the pump is properly primed the orange light will be illuminated on the right side of the chiller display PUMP SET Figure 8 Chiller Po...

Page 19: ...valve adjust knob or by pinching either the inlet or outlet hose and observing the bubbles in the flow as they are encouraged to disappear using this technique This isn t as easy as it sounds so take...

Page 20: ...for some time after flow has been established looking for any air bubbles in the clear PVC tubing and around the filter at the rear of the unit 2 Check chiller display If there is insufficient less th...

Page 21: ...nt will need to be adjusted To change the set point 1 Press or push button for more than 1 5 s to begin modifying the set point 2 Continue until the desired set point has been reached 3 The new set po...

Page 22: ...1314 900 Revision BA 250W Precision Calorimeter 17 Figure 15 Front End Layout...

Page 23: ...tic is the reduced fan noise as the system approaches set point The fan speed is directly related to the amount of cooling required This feature has been factory preset Changes while not recommended c...

Page 24: ...DO NOT APPLY MORE THAN THE MAXIMUM RATED AC OR RF TO THE LOAD USE ONLY DISTILLED WATER AS A SOURCE OF COOLANT Always allow coolant to circulate at least 3 minutes after AC or RF input power is remove...

Page 25: ...s error term by storing the RF load reflection data in memory and then applying it as a frequency correction term to obtain the final calibrated RF answer in watts Correction of Error Terms All of the...

Page 26: ...1314 900 Revision BA 250W Precision Calorimeter 21 Figure 16 Software System Files...

Page 27: ...isplay Repeat this process for as many power level points as desired for testing When finished shut off the AC source power to the input of the calorimeter and allow the coolant fluid to continue flow...

Page 28: ...and then read the RF value in the front panel display Repeat this process for as many power level points as desired for testing The power levels desired do not need to necessarily match the calibrated...

Page 29: ...oximately 20 000 hours The following should be performed at intervals of one to six months depending upon usage Remove cover to access internal components Remove accumulations of dust dirt and other o...

Page 30: ...resistance values is used by the control feedback algorithm within the CalProg program to set the requested power on the 6811B or other AC power source under automated conditions not under manual oper...

Page 31: ...er drifting Make sure chiller set point and PID parameters are correct Flow rate much less than nominal Check for blockage in fluid filter AC calibrated power equals input power Check calibration ini...

Page 32: ...ATE 0 5 058 GPM 51 to 55 FLOW_VOLUME 31 861 34 386 cm3 sec 33 14 MASS_FLOWRATE 31 784 34 302 gm_sec 33 06 SEEBECK_CONSTANT 0 04 0 06 volts C 0 04 DELTA_T 0 1 8 C 1 65 LOAD_EFFICIENCY_FACTOR 0 1 0 995...

Page 33: ...ny detailed information provided to our technicians will assist them in identifying and correcting the problem in the quickest possible manner Use a copy of the Repair and Calibration Service form pro...

Page 34: ...to fuses batteries or damage to the instrument caused by battery leakage Statement of Calibration This instrument has been inspected and tested in accordance with specifications published by TEGAM In...

Page 35: ...d Drain the individual hoses completely by removing the connectors on their respective ends 2 Place a quick connect connector with an open hose end onto the return inlet of the chiller 3 Put the end o...

Page 36: ...nical Contact Phone Number Additional Info R E P A I R I N S T R U C T I O N S E v a l u a t i o n R e p a i r C a l i b r a t i o n C a l i b r a t i o n O n l y R e p a i r o n l y P r o v i d e D a...

Reviews: