Table 5. Configuration (Continued)
Name
Status/Selection
Description
thereby avoiding unwanted effects due to an
incomplete change.
Motorpotentiometer =
Master
Motorpotentiometer =
Master
When enabled, the value of the motorpotentiometer
continuously follows the master setpoint while in
remote operation, so that no setpoint leap occurs
during the switch-over to the local setpoint.
Setpoint Error
Zero
Zero is used as the setpoint when the master setpoint is
missing.
Last valid master
setpoint
The last valid master setpoint is used as the setpoint
when the master setpoint is missing.
Last valid error setpoint
The last valid error setpoint is used as the setpoint
when the master setpoint is missing.
Local remote
configuration
Unchanged behavior
Configuration of the master's influence to the local
remote behavior.
Automatic switch to local
The unit will automatically switch to local mode when
the communication with master is interrupted.
Ignore master in local
When the unit is in local mode, data and commands
from the master will be ignored.
Configuring Flexible Link Parameters
The flexible link parameters have been designed to allow access to Thyro-PX internal data, such as
parameters and actual values.
There are up to 20 flexible link parameters for writing data and up to 20 flexible link parameters for
reading data.
Most flexible link parameters have a preconfigured, default definition, which can be modified using
the Thyro-Tool Pro PC software. All device parameters and actual values are selectable from the
drop-down list.
For special applications, the flexible link parameters can be manually configured via Ethernet IP
using the configuration assembly (see
on page 8).
Default Flexible Links
Table 6. Default flexible links
Flexible Link
Type
Default Link Setting
Flexible read-link 01 r
FLOAT
Power Controller #1: Total power - read
Flexible read-link 02 r
FLOAT
Power Controller #1: L1 Urms - read
Flexible read-link 03 r
FLOAT
Power Controller #1: L1 Irms - read
Advanced Energy
®
Thyro-PX
™
Anybus
®
Ethernet IP
57010163-00A