Table 6. Default flexible links (Continued)
Flexible Link
Type
Default Link Setting
Flexible read-link 04 r
FLOAT
Power Controller #1: L1 Power - read
Flexible read-link 05 r
FLOAT
Power Controller #1: L1 Resistance - read
Flexible read-link 06 r
FLOAT
Power Controller #1: L1 Umains - read
Flexible read-link 07 r
FLOAT
Power Controller #1: L1 Temperature - read
Flexible read-link 08 r
FLOAT
Power Controller #1: L2 Urms - read
Flexible read-link 09 r
FLOAT
Power Controller #1: L2 Irms - read
Flexible read-link 10 r
FLOAT
Power Controller #1: L2 Power - read
Flexible read-link 11 r
FLOAT
Power Controller #1: L2 Resistance - read
Flexible read-link 12 r
FLOAT
Power Controller #1: L2 Umains - read
Flexible read-link 13 r
FLOAT
Power Controller #1: L2 Temperature - read
Flexible read-link 14 r
FLOAT
Power Controller #1: L3 Urms - read
Flexible read-link 15 r
FLOAT
Power Controller #1: L3 Irms - read
Flexible read-link 16 r
FLOAT
Power Controller #1: L3 Power - read
Flexible read-link 17 r
FLOAT
Power Controller #1: L3 Resistance - read
Flexible read-link 18 r
FLOAT
Power Controller #1: L3 Umains - read
Flexible read-link 19 r
FLOAT
Power Controller #1: L3 Temperature - read
Flexible read-link 20 r
UINT32
FLOAT
Not applicable
INSTALLING OPTIONAL MODULES
DANGER:
RISK OF DEATH OR BODILY INJURY. Disconnect and lockout/tagout all sources of input
power before working on this unit or anything connected to it.
DANGER:
RISQUE DE MORT OU DE BLESSURES CORPORELLES. Débrancher et verrouiller/
étiqueter toutes les sources de puissance d’entrée avant de travailler sur cette unité ou sur
tout élément qui y est raccordé.
The optional modules may be shipped separately.
1. Verify that the unit is disconnected from all power sources.
2. Unpack each optional module at an ESD safe work space.
3. Plug each optional module into the unit.
Advanced Energy
®
Thyro-PX
™
Anybus
®
Ethernet IP
57010163-00A
Thyro-PX
™
Anybus
®
Ethernet IP
7