19
Deviating values are to be converted by percentage. The set monitor-
ing value should always be “midpoint” between the value with load
current and the value after interruption.
NOTE
Settings above 90% and below 10% are not practical. If low load cur-
rents are required, check whether a controller with a lower type current
can be used.
TAB. 1 LOAD MONITORING
NO. OF
PARALLEL
LOAD RESIS-
TANCES E.G.
NUMBER
I
LOAD NOM
/
I
TYPE/CONTROLLER
RESISTANCE
INCREASE IN
CASE
OF FAULT
RECOM-
MENDED
SETTING
FOR POTI
R205
POTI
REVOLU-
TIONS CA.
1 100%
50.0% 8.5
1
80%
40.0%
7
1
60%
Infinite
30.0%
6
1
40%
20.0%
4.5
1
20%
10.0%
2.5
2 100%
75.0% 12
2
80%
60.0%
9.5
2
60%
100,0%
45.0%
7.5
2
40%
30.0%
6
2
20%
15.0%
3.5
3 100%
83.3% 13
3
80%
66.7%
12.5
3
60%
50%
50.0% 9
3
40%
33.3% 6
4
100%
87.5%
13.5
4
80%
70.0%
12.5
4 60%
33,3%
52.5% 9
4
40%
35.0% 6
5 100%
90.0% 14
5
80%
72.0%
11.5
5 60%
25,0%
54.0% 9
5 40%
36.0% 6.5
Summary of Contents for Thyro-S 1S H 1 Series
Page 2: ...2...
Page 35: ...33 FIG 8 CONECTION DIAGRAM THYRO S 1S H 1...
Page 36: ...34 FIG 9 CONNECTING DIAGRAM 2X THYRO S 1S H 1...
Page 37: ...35 FIG 10 CONNECTING DIAGRAM THYRO S 1S H RL1...
Page 38: ...36 FIG 11 CONNECTING DIAGRAM 2X THYRO S 1S H RL1...
Page 44: ...42 11 DIMENSIONAL DRAWINGS THYRO S 1S 16H 30H THYRO S 1S 45H 60H...
Page 45: ...43 THYRO S 1S 100H THYRO S 1S 130H 170H...
Page 46: ...44 THYRO S 1S 280H...
Page 50: ......
Page 51: ......
Page 52: ......
Page 54: ......