7
2 Configuration
Programming can also be performed from the PC configuration program.
Shop Interface Input
PC Program Inputs
Purpose
Settings required at PC
INPUT A
Panel S/W-1
Panel S/W-2
Switch Input
Cable Fault
Set Zone, Text & Action
Set Zone, Text & Action=Fault
1
INPUT B
Panel S/W-3
Panel S/W-4
Switch Input
Cable Fault
Set Zone, Text & Action
INPUT C
Panel S/W-5
Panel S/W-6
EVAC Input
ALERT Input
Set Zone, Text & Action for EVAC
Set Zone, Text & Action for ALERT
INPUT D
Panel S/W-7
Switch Input
Set Zone, Text & Action
INPUT E
Panel S/W-8
Switch Input
Set Zone, Text & Action
2.1 ALERT / EVAC Input
Input C can be used to detect if a signal from an external source is off, pulsing or on continuous (e.g. to detect
an ALERT or EVAC. signal from an external clean contact). The shop interface will activate the EVAC signal if
the signal stays on for more than 1.3 seconds. If the pulsing rate is very slow, this time period can be extended
to 2.6 seconds by placing jumper J1 in position B.
The example below shows sample text for each of the inputs
– the actual device and zone text can be freely
changed to describe from where the input signal is coming for a specific application.
1
The action only needs setting to fault if monitored inputs are required. If simple switch inputs are required, leave this act
ion as “unused”.