MK Series Portable Chiller : Air-Cooled : HE INSTRUMENT
Page: 78
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
8.8
CHILLER CAPACITY AND DERATE CHART
60
50
45
40
35
30
25
20
15
10
5
0
-5
*
*
*
*
*
105%
100%
90%
80%
70%
60%
50%
40%
30%
22%
15%
9%
5%
OUTPUT
TEMPERATURE
°F
FULL
AVAILABLE %
CAPACITY
NOTES:
If operation of the chiller at less than 48°F is required, an inhibited propylene glycol solution
is required.
Consult factory for chiller operation below 20°F.
Ambient conditions affect air cooled chiller operation and capacity. Standard rating is at
95°F entering air temperature. For ambient air conditions greater than 95°F, chiller derating
will occur. For ambients of 95-105°F, select the next larger capacity chiller. For ambients
over 105°F, consult factory.
*
These ranges require special options.
Standard chiller rating is at 50°F. For all other temperature settings, output
tonnage is altered as follows: