Titan Central Chillers
Page: 49
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
G.
To change set point values :
1.
On Initial Start-up press the
Reset button to clear any errors.
2.
Press and release the Toggle
Display button once. You will see
hpSET XXX. The current set point
for head pressure cut out will be in
the place of the XXX. Use the Set
Up and Set Down buttons to change
the value. This value must not be
set higher than 50 PSI below the
relief device setting.
3.
Press and release the Toggle
Display button again to save the
new setpoint and move to the next
value. You will see spset XXX, the
suction pressure cut out value. Use
the Up and Down buttons to adjust
the value. This value must not be
set lower than the pressure that
corresponds to the freeze point of
the fluid being chilled otherwise
severe damage to the evaporator
could occur.
4.
Press and release the Toggle
Display button again to save the
value and move to the next value.
5.
You will see spDif XXX, the suction
pressure differential. This value
indicates the number of PSI the
suction pressure must rise above
the cut out value before the system
will restart. 10 PSI is usually a good
number for this value and is the
default value.
6.
Press the Toggle Display button
once more to save the value and
return to the display screen.
HEAD
PRESSURE
SUCTION
PRESSURE
HEAD
PRESSURE
SUCTION
PRESSURE
SET UP
TOGGLE DISPLAY
SET DOWN
539
505
HEAD
PRESSURE
SUCTION
PRESSURE
539
505
HEAD
PRESSURE
SUCTION
PRESSURE
SET UP
SET DOWN
10
SpDIFF
HEAD
PRESSURE
SUCTION
PRESSURE
539
505
HEAD
PRESSURE
SUCTION
PRESSURE
SET UP
TOGGLE DISPLAY
SET DOWN
505
SpSET
RESET TRIP
HEAD
PRESSURE
SUCTION
PRESSURE
539
505
HEAD
PRESSURE
SUCTION
PRESSURE
POWER ON
HEAD
PRESSURE
SUCTION
PRESSURE
539
505
HEAD
PRESSURE
SUCTION
PRESSURE
SET UP
TOGGLE DISPLAY
SET DOWN
539
hpSET
TOGGLE DISPLAY
TOGGLE DISPLAY
RESET TRIP
SET UP
SET DOWN
TOGGLE DISPLAY
SET UP
SET DOWN
TOGGLE DISPLAY
SET UP
SET DOWN
Summary of Contents for Titan
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 24: ...Page 24 THIS PAGE INTENTIONALLY BLANK ...
Page 50: ...Page 50 THIS PAGE INTENTIONALLY BLANK ...
Page 58: ...Page 58 THIS PAGE INTENTIONALLY BLANK ...
Page 74: ...Page 74 THIS PAGE INTENTIONALLY BLANK ...
Page 94: ...END 2021 ADVANTAGE ENGINEERING INC RE 20210407 ...