BC-N4 Glycol Chiller
Page: 29
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
C.
CONTROL INSTRUMENT COMPONENTS
1.
ILLUMINATED ON/OFF SWITCH: This rocker switch starts or stops the unit.
Electrical power is supplied to the unit when the switch is illuminated.
2.
UP ARROW and DOWN ARROW KEYS: Depress and hold this push button to
increase (UP ARROW) or decrease (DOWN ARROW) the setpoint temperature.
If the push button is pressed momentarily the setpoint value is incremented or
decremented by one degree. If the push button is held down the setpoint will
increase or decrease continuously.
3.
SETPOINT LOCK OUT JUMPER: This jumper controls whether the user is
allowed to reduce the setpoint below 48°F or 9°C. If the jumper is in position 1
(farthest from the SPL label) the user IS NOT ALLOWED to reduce the setpoint
below 48°F or 9°C. If the jumper is in position 2 (closest to the SPL label) the
user is allowed to reduce the setpoint to 10°F or -11°C.
4.
TEMPERATURE DISPLAY JUMPER: If this jumper is in the “F” position, the To
Process and Setpoint temperatures are displayed in Fahrenheit. If the jumper is
in the “C” position, the To Process and Setpoint temperatures are displayed in
Celsius.
5.
Probe Calibration: This pot (CALPOT 1) is used to calibrate the probe circuit.
D.
STATUS LIGHTS
1.
COMPRESSOR: Illuminates when compressor is turned on.
2.
CAPACITY CONTROL: Illuminates when capacity control system is turned on.
3.
REFRIGERANT FAULT: Illuminates when there is a high pressure or low
pressure fault. Check troubleshooting section of
this manual for more details.
High Pressure Fault. If the chiller control detects
a high pressure condition it will immediately turn
off the compressor and hot gas bypass.
Low Pressure Fault. After the compressor is
turned on, the control has a 15 second buffer
for the low pressure fault. If a low pressure
condition occurs within the first 15 seconds, the
Setpoint Lock Out Jumper Temperature Display Jumper Probe Calibration
Low Pressure Potentiometer.
Summary of Contents for BC-N4 Series
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Page 32: ...Page 32 THIS PAGE INTENTIONALLY BLANK ...
Page 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Page 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Page 62: ...Page 62 THIS PAGE INTENTIONALLY BLANK ...
Page 63: ...END 2016 ADVANTAGE ENGINEERING INC RE 09 27 2016 ...
Page 64: ......