BC-N4 Glycol Chiller
Page: 37
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
4.8 SENSOR
A.
The sensor is a solid state temperature transducer which converts
temperature input to proportional current output.
B.
To quickly test for a defective probe, switch connections between
the defective probe and a probe known to be working properly. A
defective sensor will display a “---” in the display window on the
instrument control. Please note that “---” will also display when
process temperatures are above 100°F.
4.9
COOLANT PUMP
A.
The centrifugal pump is designed to operate at a specific flow
and pressure at the maximum run load amp draw of the motor.
Too much flow can overload the motor and cause the overload
circuit to open and stop the pump.
B.
If the overload trips, check for electrical shorts, loose wires, or blown fuses. If
these check OK, reset the overload circuit and restart the chiller.
4.10 CHILLER CONTROLLER
A.
The control instrument is used for all normal set ups, diagnostics, temperature
readout and operational information. It contains the software and electronic
components which operate the control instrument.
B.
The control instrument is not field repairable. It can be easily removed and
replaced or repaired if a problem occurs.
C.
All control instruments used in Advantage water chillers are covered by the
machine’s warranty. Proprietary “tailor made” instrument are manufactured
specifically for Advantage by our affiliated company Advantage Electronics.
If you experience problems with your Advantage control instrument, it’s as easy
as 1-2-3 to execute our repair or replacement system in order to get your
Advantage equipment running.
D.
In-Warranty Service Incident
1.
Call Advantage Service at 317-887-0729 for diagnostic assistance.
2.
If a control instrument is determined to be at fault, a new or reconditioned
instrument will be sent as a replacement.
3.
Return the defective instrument freight pre-paid for a full credit. If the
faulty instrument is not returned you will need to pay for it.
E.
Out-Of-Warranty Service Incident
1.
Call Advantage Service at 317-887-0729 for diagnostic assistance.
Typical chilled
water sensor
probe with 2
pole connector.
Summary of Contents for BC-N4 Series
Page 2: ......
Page 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Page 20: ...Page 20 THIS PAGE INTENTIONALLY BLANK ...
Page 32: ...Page 32 THIS PAGE INTENTIONALLY BLANK ...
Page 48: ...Page 48 THIS PAGE INTENTIONALLY BLANK ...
Page 54: ...Page 54 THIS PAGE INTENTIONALLY BLANK ...
Page 62: ...Page 62 THIS PAGE INTENTIONALLY BLANK ...
Page 63: ...END 2016 ADVANTAGE ENGINEERING INC RE 09 27 2016 ...
Page 64: ......