BB-USR604
19
SETTING COM PORT OPERATING MODES
The operating modes of the converter are configured by the positions of DIP switches accessible on the BB-USR604
enclosure. The DIP switches are located on the top of the enclosure near the power connectors (when the unit is
positioned vertically).
•
Switches 1 and 2 configure Port 1.
•
Switches 3 and 4 configure Port 2.
•
Switches 5 and 6 configure Port 3.
•
Switches 7 and 8 configure Port 4.
Figure 13: BB-USR604 DIP Switch and Power Connectors
Operating modes are RS-232, RS-485 two-wire half-duplex, RS-485 four-wire full-duplex, and RS-422.
Port
Switch
RS-232
RS-422
RS-485
4-wire
RS-485
2-wire
Port 1
1
Off (down)
On (up)
Off (down)
On (up)
2
Off (down)
On (up)
On (up)
Off (down)
Port 2
3
Off (down)
On (up)
Off (down)
On (up)
4
Off (down)
On (up)
On (up)
Off (down)
Port 3
5
Off (down)
On (up)
Off (down)
On (up)
6
Off (down)
On (up)
On (up)
Off (down)
Port 4
7
Off (down)
On (up)
Off (down)
On (up)
8
Off (down)
On (up)
On (up)
Off (down)