PCI-1243U User Manual
70
4.7.8 High Speed Origin Return Model
Execute the reset
command
Effect the origin return
mode and set the
direction
Enter the start
command
Command buffer <- 00001000(08H)
For(+)direction: command buffer <- 01000011(43H)
For(-)direction: command buffer <- 01001011(4BH)
For FH: Command Buffer <- 00010101(15H)
The status (0)is read
Bit 3=0?
YES
Completion of
operation
NO
When the SD limit switch of the same direction as the preset direction in
¡˚ON¡±,the frequency ramps down to the rate of FL
f
Stop by origin
switch ¡˚ON¡±
Ramp down by
SD switch
¡˚ON¡±
t
When the ORG limit switch is ¡˚ON¡±, pulse output
stops and bit 3 of status 0 becomes 0