%RLOHURSHUDWLRQDQGLQWHQGHGXVH
This is a gas condensing appliance intended to generate
centralised heating. It can also be used for domestic hot
water production for civil use, but it must be appropriately
FRQQHFWHGWRDVWRUDJHWDQNVHH¿J$Q\RWKHUXVHLV
prohibited.
Maximum domestic hot water service output heat is always
guaranteed as the appliance give priority to said service.
Follow the procedure described in section 16.6 to adjust the
domestic hot water temperature.
The heating system can be created with heat elements that
work at a temperature range from 30°C to 80°C.
The boiler can be connected to a room thermostat, an
external temperature sensor or a 0-10Vdc analogue input.
This boiler must be connected to a heating and domestic
hot water production system with required output heat that
is compatible with the features of the appliance itself.
Figure 4-5 - 280T model appliance modulation
4.1.2 - Water heater operation and
intended use
This is a gas condensing appliance that must be connected
to a civil use domestic hot water production storage tank
VHH¿J
Any other use is prohibited.
4.1.3 - Wide range of modulation and
maximum performance
The appliance management program, depending on the load
of the heating system, provides for the gradual ignition of
HDFKVLQJOHKHDWLQJHOHPHQWDWPLQLPXPRXWSXWVHH¿JXUH
4-5). After which, if the load of the heating system increases,
all the heating elements progressively increase output. This
achieves modulated output from a minimum of 14kW to a
PD[LPXPFRUUHVSRQGLQJWRWKHUDWLQJRIWKHDSSOLDQFH¿JXUH
4-5 shows a 280T module with 4 heating elements), with
PD[LPXPHI¿FLHQF\FRQVHTXHQWO\PDLQWDLQHGIRUWKHHQWLUH
modulation range.
When the boiler is connected to an external temperature
VHQVRURSWLPXPHI¿FLHQF\FDQEHDFKLHYHGWKURXJKGLUHFW
FRPSHQVDWLRQRIÀRZWHPSHUDWXUHVHHVHFWLRQ