background image

96-8006123_11-03-2021

Information subject to change

15

8302 OPERATOR’S MANUAL – SECTION 5

and load, the Compensation Network 1 switch can be 
turned off and the Compensation Network 2 switch 
can be used to enable a network that provides 100k 
ohm resistance and 10 nF capacitance and should be 

used with loads that are 500 

μ

H to 1.5 mH. 

NOTE: 

It is recommended to only use one of the 

compensation networks at a time. Having SW#5 
and SW#6 both on (UP) will likely provide improper 
compensation for the load, and may result in ampli

-

fier instability.
For more information on Controlled-Current opera

-

tion, including instructions for selecting the best 
compensation setting for your application, see the 
topic “Controlled Current Operation” in the Applica

-

tions section of this manual. If neither of the avail-

able RC networks is suitable for your application, 
please contact 

AE Techron Technical Support.

SW#6: Compensation Network 1

When the 8302 amplifier is used in Controlled-

 

Current mode, the current control loop is tuned 
with an RC network. The Compensation Network 
1 switch enables the factory default RC network. 
This provides 100k ohm resistance and 2.2 nF 
capacitance and should be used with loads that 

are 50 

μ

H to 500 

μ

H

. If this default network is not 

adequate for your application and load, the Com

-

pensation Network 1 switch can be turned off and 
the Compensation Network 2 switch can be used 

to 

enable a network that provides 100k ohm resis

-

tance and 10 nF capacitance and should be used 

with loads that are 500 

μ

H to 1.5 mH.

NOTE: 

It is recommended to only use one of the 

compensation networks at a time. Having SW#5 
and SW#6 both on (UP) will likely provide improper 
compensation for the load, and may result in ampli

-

fier instability.
For more information on Controlled-Current opera

-

tion, including instructions for selecting the best 
compensation option for your application, see the 
topic “Controlled Current Operation” in the Applica

-

tions section of this manual. If neither of the avail-

able RC networks is suitable for your application, 
please contact 

AE Techron Technical Support.

SW#7: Control Configuration

When this switch is in the UP position (default), the 
amplifier will function as a stand-alone amplifier or as 
a Master amplifier in a multi-amp system. When this 
switch is in the DOWN position, the amplifier will func

-

tion as a Follower amplifier in a multi-amp system.
For more information on multi-amplifier system 
configuration and operation, see the 

Applications 

section.

SW#8: Coupling

When the Coupling DIP switch is in the UP posi

-

tion (default), the amplifier can receive and amplify 
both DC and AC signal. When this switch is in the 
DOWN position, a 30-Hz high-pass filter on the 
inputs prevents the transmission of DC signal.

SW#9 – SW#16: Gain

The amplifier gain can be adjusted from 0.16 to 40 
in increments of 0.16 using switches 9 through 16. 
All switches are additive and provide the following 
values toward the total Gain amount.
SW#9 = 20.00   

SW#13 = 1.25

SW#10 = 10.00 

SW#14 = 0.63

SW#11 = 5.00   

SW#15 = 0.31

SW#12 = 2.50   

SW#16 = 0.16

Refer to the chart in 

Appendix A

 to quickly deter

-

mine the switch settings for your desired amplifier 
gain.

SW#17: Electronic Gain Matching

The Electronic Gain Matching function serves to 
minimize circulating currents when multiple ampli

-

fiers are used in a parallel configuration. When 
enabled, the Electronic Gain Matching function 
progressively increases impedance from the volt

-

age gain as current increases, up to a mamimum 
0.20-ohm increase. This allows the amplifiers to 
operate in parallel without the use of separate 
ballast resistors. For more information on multi-
amplifier system configuration and operation, see 

the 

Applications 

section.

When the Electronic Gain Matching DIP switch is 

in the DOWN position (default), the function is dis

-

abled. When this switch is in the UP position, Gain 

Matching is enabled.

Summary of Contents for 8302

Page 1: ...8302 Operator s Manual Wide Bandwidth High Power Digital Amplifier 574 295 9495 www aetechron com 2507 Warren Street Elkhart IN 46516 ...

Page 2: ......

Page 3: ... of our authorized service centers of your need for warranty service you will receive an authorization to return the product for service All components must be shipped in a factory pack or equivalent which if needed may be obtained from us for a nominal charge We will take corrective actions and return the product to you within three weeks of the date of receipt of the defective prod uct or will m...

Page 4: ...rols Connectors 12 5 Advanced Configuration 13 5 1 DIP Switch Configurations 14 5 2 Custom Compensation 16 6 Applications 17 6 1 Emergency Standby Switch or Safety Interlock 17 6 2 Controlled Voltage vs Controlled Current Modes of Operation 17 6 3 Driving Reactive Loads 20 6 4 8302 Multi amp Systems 20 7 Maintenance 29 7 1 Clean Amplifier Filter and Grills 29 8 Troubleshooting 30 8 1 Introduction ...

Page 5: ...ng reac tive loads As frequencies increase the effective impedance of the load becomes a much larger part of the total load to be driven especially with inductive loads like coils However when driving reactive loads the 8302 is capable of receiving reprocessing and returning to the load up to 5X its rated power The result is a bench top system capable of 10 kVA output while drawing less than 2 kW ...

Page 6: ...the back of the amplifier for heated air to escape The amplifier should be mounted in a rack that is adequately ventilated and not sealed Likewise the front of the amplifier should be unobstructed to allow cool air to enter the amplifier WARNING alerts you to hazards that could result in severe injury or death Note the explanation of the hazard and the instructions for avoiding it WARNING CAUTION ...

Page 7: ...HOCK HAZARD Output potentials can be lethal Output cover must remain installed at all times to protect against HAZARDOUS LIVE VOLTAGES WARNING Figure 3 2 Connecting the Load Figure 3 3 Outputs Safety Cover 3 1 2 Output Connections Connection to the output of the amplifier is to a pair of high current output terminals Wires ter minated with 3 8 inch ring terminals are recom mended when connecting t...

Page 8: ...ed to en able disable the unbalanced input connector and DIP switch 2 can be used to enable disable the balanced input connector When these two DIP switches are placed in the UP position factory default the input connectors are enabled When the DIP switches are placed in the DOWN position the input connectors are disabled See Figure 3 5 for DIP switch locations The risk of lethal ELECTRICAL SHOCK ...

Page 9: ...hazard Connect the AC supply to the three terminal bar rier strip located on the amplifier back panel see Figures 3 6 and 3 7 Install AC inlet cover prior to connecting to the sup ply source See Figure 3 8 Figure 3 8 AC Inlet Safety Cover Start up Procedure 1 Turn down the level of your signal source 2 Place the back panel breaker switch in the ON position 3 Switch the front panel Power switch to ...

Page 10: ...ltage transform ers are not Figure 4 1 Front Panel Controls and Indicators To release the amplifier from Standby mode 1 High Low Line error Clear the over or un der voltage condition The amplifier will resume operation when the input voltage is brought within the operating range of the amplifier 2 Overtemp condition Remove the input signal from the amplifier and leave the amplifier with the Power ...

Page 11: ...ier monitors the temperature inside the high voltage transformers and in the output stage heat sinks The amber Overtemp indicator will light and the amplifier will be placed in Standby mode Figure 4 2 Back Panel Controls and Connectors when the temperature sensors detect a condition that would damage the amplifier If the Overtemp pulse is extremely short as in the case of defec tive wiring or swit...

Page 12: ...r more information Current Monitor Connector This unbalanced BNC port allows for connection to current monitor ing equipment The current monitor output is 1V 20A Voltage Monitor Connector This unbalanced BNC port allows for connection to voltage monitor ing equipment The voltage monitor output is 1V 40V Multi amp Connectors These two 9 pin D sub connectors labeled Interconnect A and Intercon nect ...

Page 13: ... Enable electronic gain matching to optimize parallel operation of two 8302 amplifiers Select and enable a synthetic impedance from 0 125 ohms to 0 875 ohms 8302 Default DIP Switch Settings Red Default DIP SWITCH SETTINGS UP DOWN 1 UNBALANCED INPUT ON OFF 2 BALANCED INPUT ON OFF 3 DC SERVO ON OFF 4 OPERATION MODE CV CC 5 COMPENSATION NETWORK 2 ON OFF 6 COMPENSATION NETWORK 1 ON OFF 7 CONTROL CONFI...

Page 14: ... for selecting the best compensation option for your application see the topic Controlled Current Operation in the Applications section of this manual If neither of the available RC networks is suitable for your application please contact AE Techron Technical Support SW 5 Compensation Network 2 When the 8302 amplifier is used in Controlled Current mode the current control loop is tuned with an RC ...

Page 15: ...ing the best compensation option for your application see the topic Controlled Current Operation in the Applica tions section of this manual If neither of the avail able RC networks is suitable for your application please contact AE Techron Technical Support SW 7 Control Configuration When this switch is in the UP position default the amplifier will function as a stand alone amplifier or as a Mast...

Page 16: ...tting one or more of the synthetic impedance switches in the UP position Refer to Figure 5 2 for all available synthetic im pedance switch settings SW 21 24 Current Limit These four switches control the current limit set tings for the amplifier When all four switches are in the UP position default the amplifier s output current is limited to 160A The current limit can be Figure 5 3 Current Limit S...

Page 17: ... AE Techron 8302 amplifiers can be field configured to operate as Voltage Amplifiers Voltage Con trolled Voltage Source or as Transconductance Amplifiers Voltage Controlled Current Source The mode selection is made via the back panel DIP switch 4 See the Advanced Configuration section for more information When configured as a Controlled Voltage source voltage amplifier the amplifier will provide a...

Page 18: ...rate your amplifier in CC mode safely and effectively We recommend that you power up and enable the amplifier in Controlled Voltage mode without at taching a load before configuring your amplifier for Controlled Current operation This will allow you to verify that the input signal and the amplifier are operating correctly Once this initial check is completed power down the amplifier attach your lo...

Page 19: ...ork 2 for your application See Figure 6 4 These compensation networks NOTE Load Resistance R is assumed to be 5 ohms STEP 3 Enable Compensation Network are enabled when Compensation Network 1 DIP switch SW 6 or Compensatlon Network 2 DIP switch SW 5 on the Master amplifier module is set to the ON UP position If your load inductance falls outside of these ranges or if your load resistance is greate...

Page 20: ...p to five times the rated power of the amplifier when driving reactive loads 6 4 8302 Multi amp Systems The 8302 amplifier may be used with one other 8302 amplifier in either a Parallel or a Push Pull Series configuration The Parallel configuration will approximately double the continuous current output to 120 Arms while the Push Pull configura tion will approximately double the voltage avail able...

Page 21: ...Principles Following these basic principles will help to ensure the safety of your equipment and personnel One Master Amplifier Multi amp configurations require one amplifier configured as a Master amplifier and the second amplifier in the system configured as a Follower amplifier Use Only 8302 Amplifiers Use only AE Techron 8302 amplifers to construct a 8302 multiamp system Do not combine differe...

Page 22: ...n be performed using an oscillo scope or a floating digital multimeter with a resolu tion of at least three digits Both testing methods are provided below Testing Using an Oscilloscope 1 Connect from a signal generator to the BNC or WECO signal input connector on the back panel of the Master amplifier Note that if the WECO connector is used for signal input DIP switch 1 on the Master amplifier sho...

Page 23: ...ector and the GND bus bar 6 Adjust your signal source to input a 1 kHz 2 5 Vrms sinewave into the Master amplifier input The measured output should be at or very near to 100 Vrms Record the measured output 7 Connect the digital multimeter between the Follower amplifier s Output connector and the GND bus bar The measured output should be at or very near to 100 Vrms Record the mea sured output 8 Set...

Page 24: ...IMON on both the Master and the Fol lower amplifiers 2 Turn down the level of your signal source 3 Make sure both amplifier s back panel breaker switches are in the ON position and then press the Power switch on each of the amplifier s front panels to energize the amplifiers 4 Wait for the green RUN LED to illuminate on the amplifier 5 Adjust your signal source to input a 1 kHz sine wave of 100 mV...

Page 25: ...mplifier continue with the system setup IMPORTANT If current exceeds 2A 0 1V from either amplifier DO NOT complete the system setup Contact AE Techron Techni cal Support for assistance 8 Slowly raise the input voltage from 100 mV to to 2 5V while continuing to monitor current at IMON IMPORTANT If current exceeds 2A 0 1V from either amplifier at any time DO NOT complete the system setup Contact AE ...

Page 26: ...al or other terminal suitable for the system output and adaptable to the connectors on the load Terminate the other end of each cable with 3 8 inch ring terminal ends to facilitate con nection to each amplifier s output connec tors B Build a Bridge cable Terminate both ends of the cable with 3 8 inch ring terminal ends to facilitate connection to each ampli fier s output connectors 4 Connect the L...

Page 27: ...oltage or controlled current operation and amplifier compensation Because the amplifiers in a multiamp system are interlocked the main and fault status indicators of both amplifiers in the system must be considered to determine the current status and the necessary remedies to return the system to operational status when a fault condition occurs Run Standby Indicators When each amplifier in a multi...

Page 28: ...ers will return automatically to Run mode If the High Low Line indicator does not turn off or if the system does not return from Standby one or both amplifiers may require servicing See the Troubleshooting section in this manual for more information Overtemp Both amplifiers monitors the tempera ture inside its high voltage transformers and in the output stage heat sinks The amber Overtemp indicato...

Page 29: ...magnets Pull out on the grill to re lease it from the front panel 3 Remove the filter located behind the front grill 4 Using a vacuum cleaner vacuum the front ven tilation grill the grill filter and the back ventila tion exit grill 5 Using a damp cloth clean the amplifier front panel and the rear ventilation grills Also use the damp cloth to clean the front grill and filter If necessary these can ...

Page 30: ... if the AC supply into the amplifier is higher or lower than the operable range First check to make sure the amplifier s back panel breaker is turned on Next check the voltage level of the AC supply If the AC mains voltage is more than 10 outside the range of the operating voltage increase or reduce the AC mains voltage to the proper level When the line voltage condition is corrected the amplifier...

Page 31: ...LED is Illuminated The 8302 contains protection circuitry that disables the amplifier if an output stage is behaving abnor mally This usually indicates an output transistor has shorted To clear the Fault condition follow these steps 1 Turn off the signal source 2 Turn off the AC mains 3 Turn AC mains power back on If the Fault LED doesn t illuminate again press the Power switch to place the amplif...

Page 32: ... OFF ON ON 36 88 ON ON ON OFF ON OFF ON ON 36 72 ON ON ON OFF ON OFF ON 36 56 ON ON ON OFF ON OFF OFF ON 36 41 ON ON ON OFF ON OFF OFF OFF 36 25 ON ON ON OFF OFF ON ON ON 36 10 ON ON ON OFF OFF ON ON 35 94 ON ON ON OFF OFF ON ON 35 79 ON ON ON OFF OFF ON 35 63 ON ON ON OFF OFF OFF ON ON 35 47 ON ON ON OFF OFF OFF ON 35 31 ON ON ON OFF OFF OFF OFF ON 35 16 ON ON ON OFF OFF OFF OFF OFF 35 00 ON ON O...

Page 33: ...FF OFF OFF OFF ON 30 31 ON ON OFF OFF OFF OFF OFF ON 30 16 ON ON OFF OFF OFF OFF OFF OFF 30 00 ON OFF ON ON ON ON ON ON 29 85 ON OFF ON ON ON ON ON OFF 29 69 ON OFF ON ON ON ON OFF ON 29 54 ON OFF ON ON ON ON OFF OFF 29 38 ON OFF ON ON ON OFF ON ON 29 22 ON OFF ON ON ON OFF ON OFF 29 06 ON OFF ON ON ON OFF OFF ON 28 91 ON OFF ON ON ON OFF OFF OFF 28 75 ON OFF ON ON OFF ON ON ON 28 60 ON OFF ON ON ...

Page 34: ... OFF OFF ON OFF 22 81 ON OFF OFF ON OFF OFF OFF ON 22 66 ON OFF OFF ON OFF OFF OFF OFF 22 50 ON OFF OFF OFF ON ON ON ON 22 35 ON OFF OFF OFF ON ON ON 22 19 ON OFF OFF OFF ON ON ON 22 04 ON OFF OFF OFF ON ON 21 88 ON OFF OFF OFF ON OFF ON ON 21 72 ON OFF OFF OFF ON OFF ON 21 56 ON OFF OFF OFF ON OFF OFF ON 21 41 ON OFF OFF OFF ON OFF OFF OFF 21 25 ON OFF OFF OFF OFF ON ON ON 21 10 ON OFF OFF OFF OF...

Page 35: ... ON ON OFF OFF OFF OFF OFF 15 00 OFF ON OFF ON ON ON ON ON 14 85 OFF ON OFF ON ON ON ON OFF 14 69 OFF ON OFF ON ON ON OFF ON 14 54 OFF ON OFF ON ON ON OFF OFF 14 38 OFF ON OFF ON ON OFF ON ON 14 22 OFF ON OFF ON ON OFF ON OFF 14 06 OFF ON OFF ON ON OFF OFF ON 13 91 OFF ON OFF ON ON OFF OFF OFF 13 75 OFF ON OFF ON OFF ON ON ON 13 60 OFF ON OFF ON OFF ON ON OFF 13 44 OFF ON OFF ON OFF ON OFF ON 13 2...

Page 36: ...OFF OFF ON OFF ON ON ON ON 7 35 OFF OFF ON OFF ON ON ON OFF 7 19 OFF OFF ON OFF ON ON OFF ON 7 04 OFF OFF ON OFF ON ON OFF OFF 6 88 OFF OFF ON OFF ON OFF ON ON 6 72 OFF OFF ON OFF ON OFF ON OFF 6 56 OFF OFF ON OFF ON OFF OFF ON 6 41 OFF OFF ON OFF ON OFF OFF OFF 6 25 OFF OFF ON OFF OFF ON ON ON 6 10 OFF OFF ON OFF OFF ON ON OFF 5 94 OFF OFF ON OFF OFF ON OFF ON 5 79 OFF OFF ON OFF OFF ON OFF OFF 5...

Page 37: ...N ON OFF 2 19 OFF OFF OFF OFF ON ON OFF ON 2 04 OFF OFF OFF OFF ON ON OFF OFF 1 88 OFF OFF OFF OFF ON OFF ON ON 1 72 OFF OFF OFF OFF ON OFF ON OFF 1 56 OFF OFF OFF OFF ON OFF OFF ON 1 41 OFF OFF OFF OFF ON OFF OFF OFF 1 25 OFF OFF OFF OFF OFF ON ON ON 1 10 OFF OFF OFF OFF OFF ON ON OFF 0 94 OFF OFF OFF OFF OFF ON OFF ON 0 79 OFF OFF OFF OFF OFF ON OFF OFF 0 63 OFF OFF OFF OFF OFF OFF ON ON 0 47 OF...

Reviews: