1 Safety Description
User Manual
4
Generally, the working temperature of the UPS is -5
℃
~
+40
℃
and the relative humidity is
0%RH
~
95%RH with no condensation (The recommended working temperature is
20
℃
~25
℃
and the recommended relative humidity is about 50%).
Put UPS in the flat floor without vibration and the vertical gradient is less than 5°. Keep
good ventilation around the UPS. The clearance between the rear or the side of UPS and
adjacent devices or wall should be at least 300mm
~
500mm. Poor ventilation will rise
temperature inside the UPS, which will reduce the working life of inner components and
then affect the working life of UPS.
The recommended altitude is lower than 1000m. If exceeding 1000m, it needs to decrease
the rated power according to GB3859.2-93 to use.