Batt. Capacity (Ah)
9
Akü kapasitesi
Batt. Paral. Arms
2
Akü paralel kol sayısı
Current Offset Lmt.
ENTER ‘OK’
6.3
1)
Make all the circuit breakers of UPS off. Drain DC bus energy.
2)
There are four notches on SW2 switch. The switch 1 must be on, in the shown group in
Picture 2.The PWM sockets of J36-J37 will be unplugged on the main board as shown in
Picture 2.
3)
Plug the serial cable into the “RS232” slot on the rear side of the UPS. The J1 inverter cable
socket which comes from DB9 socket and existing in the UPS will be plugged on the main
board of the UPS
.
4)
Connection between UPS and computer is made by chipset FTDI/FT232RL converter.
5) Run the “C2000 programmer” on computer and select related to COM port and rectifier file
as shown Picture 03-06
Picture 03.
Summary of Contents for IST5 Series
Page 2: ...2 2 SERVICE MANUAL 10 15 20 30 40 60 80 100 120 160 200 300 KVA...
Page 6: ...9 9 2 PRODUCT DESCRIPTION 2 1 General View 10 15 20 30 40KVA...
Page 7: ...10 10 60 80KVA...
Page 8: ...11 11 100 120 160 200 300 KVA...
Page 13: ...16 16 2 5 Side Interior View 10 15 20 30 40KVA...
Page 16: ...19 19 2 7 Electrical Connections...
Page 35: ...38 38...
Page 36: ...39 39...
Page 51: ...54 54 30 40KVA 60 80 100 120 160 200 300 KVA...
Page 54: ...57 57...
Page 71: ...74 74 1 Turn CB2 ON 10 15 20KVA 30 40KVA...
Page 72: ...75 75 60 80 100 120KVA 2 Stop the UPS using the user front panel Main menu Control Stop...
Page 73: ...76 76 3 Turn CB1 CB3 and CB4 OFF 10 15 20KVA 30 40KVA...
Page 100: ...103 103 Signal Flow Diagram zole trafo means isolated transformer...
Page 102: ...105 105 20 30KVA IGBT Driver 40KVA IGBT Driver...