Installation Instruction
6 IST5 Tower UPS 10kVA~40kVA User Manual
Rectifier/
Discharger
Main Input
Static Switch
Manual Bypass
Inverter
Charger
Load
Battery
Bypass Input
Output Switch
Fig. 2-4 Bypass mode operation diagram
2.3.4 Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load
when the UPS becomes unavailable e.g. during a maintenance procedure. (See Fig.2-
5).
Main Input
Manual Bypass
Battery
Bypass Input
Output Switch
Rectifier/
Discharger
Inverter
Charger
Load
Fig .2-5 Maintenance mode operation diagram
Danger
During Maintenance mode, dangerous voltages are present on the terminal of input, output and
neutral, even with all the modules and the LCD turned off.
2.3.5 ECO Mode
To improve system efficiency, UPS rack system works in Bypass mode at normal time,
and inverter is standby. When the utility fails, the UPS transfers to Battery Mode and
the inverter powers the loads.